Connect the AC connector to the inverter's AC terminal;
e.
a click indicates that the connection is in place, as shown
in Fig. 31:
Fig. 31. Connecting the AC connector to the inverter's AC terminal.
Insert the relevant AC circuit breakers in between,
f.
as shown in the table below:
Model
EQX2 2001-S
EQX2 3001-S
EQX2 3002-S
EQX2 3002-SX
EQX2 4002-S
EQX2 4002-SX
EQX2 5002-S
EQX2 5002-SX
EQX2 6002-S
EQX2 6002-SX
EQX2 8002-SX
EQX2 10002-SX
Tab. 10. AC protections, by model.
58
Thermal-
Over-
magnetic
Differen-
fuse. Max.
voltage
circuit
tial relay
protection
breaker
(1/phase)
2P 16A
Curve C
2P 25A
30mA
2P 20A
Class A
Curve C
2P 25A
Curve C
40kA 230V
2P 40A
2P 30A
TT Type II
30mA
Curve C
Class A
2P 40A
Curve C
2P 50A
2P 63A
Curve C
30mA
2P 63A
Class A
Curve C
Connect the other end of the hose to the AC circuit breaker
g.
in the junction box, downstream of the connection's IGA.
L
N
GND
Fig. 32. Electrical wiring diagram.
Previous
value
For the connection of equipment with 24h monitoring, see
manual EL23300.