Descargar Imprimir esta página

AERMEC MODUCONTROL Manual De Uso página 46

Regulación electrónica
Ocultar thumbs Ver también para MODUCONTROL:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Maximum heating set-point limit that can be set
Index - String
MIN value
MAX value
Parameter function
t LSP
15 °C
65°C
This parameter indicates the maximum temperature of the water produced by the unit in heat mode.
13 INSTALLER 2 MENU
To access the installer 2 menu, follow the same procedure described for the INSTALLER menu; the only difference is the value of the password, which is 31.
 PASSWORD = 031
Fig. 9a
Fig. 10a
WARNING The following parameters must only be modified by qualified personnel authorised to install the unit.
46

Publicidad

loading