Instruction Symbols - S&P CADB-N TERMO-REG 05 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. HANDLING
Before installing, make sure that the device to be used for moving and/or raising the product has
suffi cient capacity.

6. INSTRUCTION SYMBOLS

WATER
COIL
ELECTRIC
HEATER
7. INSTALLATION
7.1. INTRODUCTION
Horizontal models size 05, 08, 12, 18, 23 and 30
Horizontally confi gured models are designed to be installed hanging from the ceiling or located behind
a false ceiling.
The 05, 08, 12, 18, 23 and 30 models have four metal brackets, one on each lower corner. Using studded
rods (Ø 8 mm), it can be secured to the ceiling and levelled.
The installer must make sure that the ceiling structure and the securing elements can bear the weight
of the device, taking into account that it is a dynamic load.
To prevent the transmission of vibrations from the unit to the rest of the installation, it is necessary
that the installer use specifi c isolation elements, such as antivibration devices in the supports, fl exible
sleeves between the unit and the ducts, and fl exible couplings between the water connections and the
pipelines.
Danger signs
CENTRIFUGAL
FAN
DOUBLE THICKNESS
ISOLATION
Prohibition signs
FILTER
DRAIN
33
EXHAUST AIR
FRESH AIR

Publicidad

Tabla de contenido
loading

Tabla de contenido