Factory seetings:
To exit the setup menu press the button ON / OFF on the console.
10.2.1.7. Digital input confi guration
The digital input can be confi gured to perform the REMOTE ON/OFF functionality or BOOST function.
On/Off Remote function
The situation of closed digital input corresponds to the order of remote Off. Digital input open
corresponds to the Remote On command.
Particularities: When the equipment is stopeed via remote control, it can not be started remotely
(It is necessary to runt he unit by means of the hand controller).
In post heating versions the stop of fans is delayed (3 min.) from the moment of receive the
STOP order.
Boost function
By opening/closing the remote contact it is possible to disable / enable the Boost function. In
this operating mode, the fans should be at maximum speed for a minimum time of 30 minutes.
To activate the Boost function it is necessary to activate the external contacts for al least 3 se-
conds. The Boost will then be triggered for 30 minutes.
10.2.1.8. Reset the maintenance counter Period
It is possible to reset the hour counter to receive the alarm for periodic maintenance
From the time the reset is performed, the counter will start counting the hours that have been
set in the parameter (installer menu) until a new alarm is generated by periodic maintenance.
To perform the reset of the counter in maintenance period, proceed as follows:
1. Turn the unit ON using the ON/OFF button and proceed as follows: