JBM-100-E
JBM-100-EP
JBM-100-L-E
JBM-100-L-EP
ENGLISH
PTB 09 ATEX 1056 U
IECEx PTB 09.0027U
Rated voltage:
Ambient temperature: JBM-100-E(P): –50°C to +56°C**
**: Special conditions for safe use may apply.
Ex e(m) II T*
* For system Temperature Code, see heating cable or design documentation.
Rated voltage:
Ambient temperature: –40°C to +40°C
BR-EX e II
BR-Ex em II
Maximum pipe temperature:
Heater type
BTV
QTVR
XTV
KTV
VPL
VPL: maximum pipe temperature in dependence
of heat type and voltage
Heater Type 230 Vac
5VPL2-CT
230°C
10VPL2-CT
210°C
15VPL2-CT
180°C
20VPL2-CT
150°C
Heater Type 385 Vac
5VPL4-CT
230°C
10VPL4-CT
215°C
15VPL4-CT
195°C
20VPL4-CT
150°C
Special conditions for safe use using ATEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas
(for example GL-38-M25-METAL).
For voltages >254Vac and BTV, QTVR, XTV or KTV heating cables:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas
(for example GL-38-M25-METAL).
Installation instruction for multiple entry power connection with junction box.
For use with all Raychem BTV-, QTVR-, XTV-,KTV- and VPL-heat ing ca bles.
WARNING: To prevent elec tri cal shock, short cir cuit or arc ing, this prod uct must be
in stalled cor rect ly and water ingress must be avoid ed before and during the in stal la tion.
Before installing this product, read the installation instructions completely.
Avoid skin and eye contact with sealing grease.
Consult Raychem safety data sheet VEN0033EA (INSTALL-027).
II 2G Ex e (e mb) II
II 2D Ex tD (tD mbD) A21 IP66
Ex e (e mb) II
Ex tD (tD mbD) A21 IP66
JBM-100-E(P): 480 Vac**
JBM-100-L-E(P): 254 Vac
JBM-100-L-E(P): –40°C to +40°C
277 Vac
T
continuous
max
65°C
110°C
121°C
150°C
See tables below
254 Vac
277 Vac
225°C
225°C
200°C
195°C
145°C
105°C
Not allowed
400 Vac
480 Vac
230°C
230°C
215°C
205°C
195°C
160°C
150°C
150°C
T
intermittent
max
1000h cumulative
85°C
110°C
250°C
250°C
–
VPL: Maximum pipe temperature
in dependence
≤ 150°C
30 A
30 A
30 A
30 A
≤ 150°C
30 A
30 A
30 A
30 A
T
power off
max
–
–
–
–
260°C
≤ 180°C
≤ 230°C
25 A
20 A
25 A
20 A
25 A
–
–
–
≤ 180°C
≤ 230°C
25 A
20 A
25 A
20 A
25 A
–
–
–