MICROCONTROLLER-BASED OIL BURNER CONTROLS FOR THE STARTUP,
SUPERVISION AND CONTROL OF FORCED DRAFT OIL BURNERS IN INTERMITTENT
OPERATION.
Funzionamento
Lockout reset button «EK...» is the key operating element for
resetting the burner control and for activating / deactivating
EK
the diagnostic func-tions.
The multicolor signal lamp (LED) in the lockout reset button
is the key indicating element for both visual diagnostics and
interface diagnostics.
RED
YELLOW
GREEN
Both «EK...» and LED are located under the transparent cover of the lockout reset but-ton.
There are 2 diagnostic choices:
1.
Visual diagnostics: Operational status indication or diagnostics of the cause of fault.
2. Interface diagnostics: With the help of the interface adapter OCI400 and PC soft-ware ACS400 or flue gas analyzers of
different makes (refer to Data Sheet N7614).
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color codes according to the color code table
given below. Interface diagnostics is activated by pressing the lockout reset button for at least 3 seconds (refer to Data Sheet
N7614). If, by accident, interface diagnostics has been activated, in which case the slightly red light of the signal lamp flickers, it
can be deactivated by pressing again the lockout re-set button for at least 3 seconds. The instant of switching over is indicated
by a yellow light pulse.
O p e r a t i n g
position
Color code tablei
Operational status indication
Color code table for multicolor signal lamp (LED)
Status
Waiting time «tw», other waiting states
Oil preheater on, waiting time «tw»
Ignition phase, ignition controlled
Operation, flame o.k.
Operation, flame not o.k.
Undervoltage
Fault, alarm
Error code output (refer to «Error code ta-ble»)
Extraneous light on burner startup
Interface diagnostics
Legend
OFF
RED
Color code
....................................
...................................
.
.
YELLOW
GREEN
25 / 56
0006080405_201612
O p e r a t i n g
position
Interface diagnostics
PC / analyzer
Color
Off
yellow
Flashing yellow
.
green
Flashing green
Yellow-red
Red
Flashing red
Green - red