Siemens RVL479 Instrucciones De Montaje página 29

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 132
68
Maximum optimum
shutdown
69
Maximum limitation
of room temperature
70
Effect of room tem-
perature
71
Boost of room tem-
perature setpoint
with boost heating
72
Parallel shift of
heating curve
73
Type of heating
curve adjustment
Block "Three-position actuator for heating circuit"
81
Maximum limitation
of flow temperature
82
Minimum limitation
of flow temperature
83
Maximum increase
rate of flow tem-
perature
84
Excess temperature
mixing valve
85
Actuator running
time
Building Technologies
0:00 h
(0:00...6:00)
......................
--.- °C
(--.- / 0...35)
°C
...................
4
(0...20)
.........................
5 °C
(0...20)
°C
...................
0.0 °C
°C
(−4.5...+4.5)
...................
0
(0...2)
.........................
--- °C
(--- / 0...140)
°C
...................
--- °C
(--- / 0...140)
°C
...................
--- °C/h
(--- / 1...600)
°C/h
..............
10 °C
(0...50)
°C
...................
120 s
(30...873)
......................
74 319 0620 0 a
Maximum forward shift for
h
switching off before end of
occupancy
setting 0:00 = optimization of
switching off disabled
Setting --.- = limitation disabled
Only with room temperature
sensor / room unit
Compensation factor for effect
of room temperature
Function possible only with
room unit / room temperature
sensor
Value in °C room temperature
(remote setting via data bus)
0 = analog adjustment
1 = digital adjustment on the
controller and via bus
2 = digital adjustment via bus
only
Setting --- = function disabled
(e.g. for floor heating 55 °C)
Setting --- = function disabled
Setting --- = function disabled
(function prevents cracking
noise in piping)
For use in interconnected plants
(setpoint elevation for primary
controller)
s
17.04.2008
en
29/152