Document No. 129-541
Installation Instructions
April 2, 2013
F1

DIP Switches

NOTE: ● The black position indicates the active switch setting.
● For Siemens FHC/LRC pulsed control signal applications, see Section F2.
● On initial power-up, and after a power-fail event, the GNP actuators require up to 90 seconds to fully
charge their capacitors. During this time the actuator will respond to positioning commands, but will not
power-fail until the capacitors are fully charged.
0 to 10Vdc 2 to 10Vdc 0 to 20mA
NOTE: An improperly tuned loop will cause excessive repositioning that will shorten the life of the actuator.
NOTE: Une boucle mal réglée va entrainer des repositionnements excessifs qui réduiront la vie du servomoteur.
NOTA: Un circulo entunado incorrectamente causara reposiciones excesivas que acortaran la vida del actuador.
Page 6 of 10
Communtateur DIP
Modulating Control
4 to 20mA
Rotation Direction
Figure 9. Setting.
Figure 10. Siemens Factory Default Setting.
DIP Contacto
2-Position Control
Floating Control
Power Fail Direction
GNP19.... Only
Siemens Industry, Inc.