Wiring Diagrams; Schémas De Raccordement; Diagramas De Cableado - Siemens OpenAir GNP Serie Instrucciones De Montaje

Tabla de contenido

Publicidad

Document No. 129-541
Installation Instructions
April 2, 2013
G

Wiring diagrams

CAUTION:
Unused wires must be properly terminated.
Les fils inutilisés doivent être correctement bouclés.
Los alambres inusitados deben ser terminados correctamente.
Page 8 of 10
Schémas de raccordement
Control Signal
24 Vac/dc
Supply
(24 Vac/dc)
1
7
M
2
9
Common
Feedback
(0 to 10 Vdc)
Figure 12. Two-Position Control.
Control Signal
24 Vac/dc
Supply
(24 Vac/dc)
1
7
8
M
2
9
Common
Feedback
(0 to 10 Vdc)
Figure 13. Floating Control.
Control Signal
0(2) to 10 Vdc
0(4) to 20 mA
Supply
(24 Vac/dc)
1
8
M
2
9
Common
Feedback
(0 to 10 Vdc)
Figure 14. Modulating Control.

Diagramas de cableado

24 Vac to 250 Vac
12 to 30 Vdc
S1
S4
S2 S3
S5 S6
24 Vac to 250 Vac
12 to 30 Vdc
S1
S4
A
B
S2 S3
S5 S6
24 Vac to 250 Vac
12 to 30 Vdc
S1
S4
S2 S3
S5 S6
2-position control
Commande TOR
Control a 2 puntos
NOTE: 2-position control
requires three
wires.
REMARQUE : La
commande TOR
exige trois fils.
NOTA : El control de 2
posiciones
requiere tres
alambres
Floating control
Commande à action flottante
Control de flotación
Modulating control
Commande progressive
Control continuo