Section 3
IntelliComm Communication Center
The Pentair IntelliComm communication center provides automatic control of the IntelliFlo pump.
The IntelliComm provides four pairs of input terminal connections. These inputs connectors are
actuated by either 15 VAC to 240 VAC or 15 VDC to 100 VDC from the source device such as an
automation controller, heater, or heat pump. Using the device's inputs, the four IntelliFlo external
control programs can be enabled. If more than one input is active, the highest program number
will be communicated to the IntelliFlo pump.
The IntelliFlo pump is programmed to run at a specific speed for each input.
Ground terminal
Attach incoming IntelliComm AC
power wires to AC terminals
Attach control input wires to
terminals 3 through 10
1 and 2
IntelliComm Communication Center
Attach IntelliFlo communication cable
wires to terminals 11 and 12
Ground terminal