6. Test run
6.1. Before test run
► After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of 1 phase in
the supply.
► Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 MΩ.
Controller interface
Function buttons
Fig. 6-1
Step 1 Switch the remote controller to "Test run".
Select "Service" from the Main menu, and press the
When the Service menu is selected, a window will appear asking for the password. (Fig. 6-2)
To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the
(0 through 9) with the
or
button. Then, press the
F3
F4
Note: The initial maintenance password is "9999". Change the default password as necessary to prevent unauthorized access.
Have the password available for those who need it.
Note: If you forget your maintenance password, you can initialize the password to the default password "9999" by pressing and holding the
simultaneously for three seconds on the maintenance password setting screen.
Select "Test run" with the
or
F1
F2
Select "Test run" with the
or
F1
F2
Service menu
Enter maintenance password
Select:
Cursor
F1
F2
F3
F4
Fig. 6-2
button.
button.
button, and press the
button. (Fig. 6-3)
button, and press the
button. (Fig. 6-4)
S
e
v r
c i
e
m
e
n
u
Test run
Input maintenance info.
Function setting
Check
Self check
M
a
n i
m
e
n
: u
C
u
s r
r o
F1
F2
F3
Fig. 6-3
► Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
6.2. Test run
The following 3 methods are available.
6.2.1. Using wired remote controller (Fig. 6-1)
▌
[ON/OFF] button
Press to turn ON/OFF the indoor unit.
▌
[SELECT] button
Press to save the setting.
▌
[RETURN] button
Press to return to the previous screen.
▌
[MENU] button
Press to bring up the Main menu.
▌
Backlit LCD
Operation settings will appear.
When the backlight is off, pressing any button turns the backlight on and it will
stay lit for a certain period of time depending on the screen.
When the backlight is off, pressing any button turns the backlight on and does
not perform its function. (except for the [ON/OFF] button)
▌
ON/OFF lamp
This lamp lights up in green while the unit is in operation. It blinks while the
remote controller is starting up or when there is an error.
▌
Function button [F1]
Main display: Press to change the operation mode.
Main menu: Press to move the cursor down.
▌
Function button [F2]
Main display: Press to decrease temperature.
Main menu: Press to move the cursor up.
▌
Function button [F3]
Main display: Press to increase temperature.
Main menu: Press to go to the previous page.
▌
Function button [F4]
Main display: Press to change the fan speed.
Main menu: Press to go to the next page.
Test run menu
Test run
Drain pump test run
Service menu:
Cursor
F4
F1
F2
Fig. 6-4
F1
or
F2
button, and set each number
F1
and
F3
F4
F2
buttons
13