9.4 SUPERVISOR PARAMETERS

ANALOG VARIABLES
BMS
Description
Address
1
Adsorber Inlet Temperature
2
Purge Air Temperature
3
Dew Point Temperature
4
Heater Temperature 1
5
Heater Temperature 2
8
Set Dew Point Fitted
16
Thermal Mass Temperature
50
Pressure Column 1
51
Pressure Column 2
52
Discharge Refrigerant Temperature
67
Optional (Ambient Temperature )
INTEGER VARIABLES
1
2
17
20
21
22
23
24
25
26
28
29
30
31
32
33
34
35
36
37
43
51
Software Release
52
Software Date Year
53
Software Date Month
54
Software Date Day
59
60
Operating Software
71
Moisture Drain ON
72
Moisture Drain OFF
74
Modbus Address
75
Baud Rate
76
Money Type
78
84
Delay Change Filter Year
85
Delay Change Filter Month
86
Delay Change Filter Day
90
Optional (Set ambient Temperature )
Default
"Read/
Variable name
Write"
0
R
ADInletTemp
0
R
PurgeAirTemp
0
R
DewpointTempDisplay
0
R
HeaterOutletTemp_A
0
R
HeaterOutletTemp_B
-40
R/W
SetPDP
0
R
ThermalMassTemp
0
R
Pressure_Col1
0
R
Pressure_Col2
0
R
DischRefrTemp
0
R
AmbientProbe
90
R/W
SetAt70
10
R/W
RitTc
146
R/W
SetAt
5
R/W
Set_i
0
R
TimerFaseAdsorbtionCol1
0
R
TimerFaseAdsorbtionCol2
0
R
TimerFaseHeatingCol1
0
R
TimerFaseHeatingCol2
0
R
TimerFaseCoolingCol1
0
R
TimerFaseCoolingCol2
59
R/W
SetHt40
30
R/W
SetCt40
10
R
Htmax
10
R
Htmax1
10
R
CtMax
10
R
SetCtMax
0
R
TDrainCol1
0
R
TDrainCol2
0
R
TimerFasePressurizTotaleCol1
0
R
TimerFasePressurizTotaleCol2
150
R/W
SetTHeat
0
R
SW_Release
0
R
SW_Date_Year
0
R
SW_Date_Month
0
R
SW_Date_Day
8
R/W
UnitModel
2
R
OperatingSoftware
5
R/W
ParMoistureDrainModeTon
120
R/W
ParMoistureDrainModeToff
1
R/W
BMS_ADDRESS
3
R/W
BaudRate
0
R/W
MoneyType
0
R/W
SelezioneDeltaKwh
0
R
UltimoCambioFiltroAnno
1
R
UltimoCambioFiltroMese
1
R
UltimoCambioFiltroGiorno
13.0
R/W
SetTambiente
ATT060-090
91
Optional (Diff ambient Temperature )
92
Ooptional (Delay summer Day)
93
Ooptional (Delay summer Hour)
94
Ooptional (Delay summer Day)
95
Optional (Offset Dew Point )
96
Optional (set Dew point )
98
Optional (Diff Dew point )
101
Working Pressure
113
Mode Moisture Drain
161
2.0
R/W
DiffTambiente
0
R/W
DeleyEstateGiorni
0
R/W
DelayEstateOre
1
R/W
DelayEstateGiorni
0
R/W
OffsetDewPoint
10
R/W
SetPointDewpoint
0
R/W
DiffDewPoint
0
R
WorkingPressure
1
R/W
ParMoistureDrainMode
0
R
NewSetPDP
10

Publicidad