CL440, CL460
A
NOTICE! Risk of damage
Do not use extension cords or ungrounded (two prong) adapters.
The cooling device is designed for free-standing installation, but can be built-in if the
following conditions are complied with to ensure satisfactory operation and maxi-
mum cooling efficiency.
• The cooling device must be levelled carefully to ensure proper function.
• For the glass door version: When ambient humidity is above 65 % in 25 °C ambi-
ent temperature, moisture will condense on the door.
• The socket outlet for the mains connection must be freely accessible.
• When the cooling device is positioned, the supply cord must not be trapped or
damaged.
Ventilation (fig. 3, page 4)
• Ventilation must be provided as shown in alternatives A, B, C or D.
• Ventilation grills (1), if used, must have openings of at least 200 cm² each.
• The minimum clearance between the cooling device's back and the surrounding
structure should be as follows:
No. in
fig. 3, page 4
2
3
• The ventilation duct must at least measure 105 mm x the width of the cooling
device.
• Only the entire cooling unit must project into the ventilation duct as shown.
• Air passing through the ventilation duct must not be preheated by any source of
heat.
• The ventilation duct must be kept free from any obstacles. Especially portable
multi socket outlets or portable power supplies, which can get warm, must not
be kept at the rear of the cooling device.
5.1
Fixing the cooling device
➤ Fix the cooling device through its fixing feet as shown (fig. 2, page 3).
EN
Min. distance
20 mm
105 mm
Installation
17