Electromagnetic Compatibility; Compliance With International Standards - Chauvin Arnoux AmpFLEX A100 Serie Manual De Instrucciones

Sensores de corriente
Ocultar thumbs Ver también para AmpFLEX A100 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.5 COMPLIANCE WITH ELECTRICAL STANDARDS
4.5.1 Electrical safety (in line with IEC 1010-1)
Double insulation
Installation category III
Operating voltage: 1000 V
Pollution level 2

4.5.2 Electromagnetic compatibility

Immunity: meets BF EN 61326 - 1 Industrial environment category
- Electrostatic discharge (meets EN 61000-4-2)
8 kV in air - level 3 - class B
4 kV on contact - level 2 - class B
- 10V/m radiated electromagnetic field (in line with EN 61000-4-3)
Class B
- Rapid transients (in line with EN 61000-4-4)
1 kV - level 2 - class B
- Electric shocks (in line with EN 61000-4-5)
6 kV - class B
4.5.3 Mechanical protection
Waterproofing (in line with EN 60529)
- Box - protection index IP40
- Flexible probe : protection index IP40
Shocks: 100g (in line with IEC 68-2-27)
Drop test: 1m (in line with IEC 68-2-32)
Vibrations (in line with IEC 68-2-6)
4.5.4 Auto-extinguishability rating
Flexible probe: V0 (in line with UL 94)
4.5.5 Resistance to chemical products
Flexible probe: resistant to oils and aliphatic hydrocarbons
18

Publicidad

Tabla de contenido
loading

Tabla de contenido