4 Transportation and assembly
24
| Comply with the following clearances during installation:
|
300 mm above
|
300 mm below
|
150 mm to the side
|
40 mm from the wall
(the wall clearance of 40 mm is guaranteed by the wall
bracket provided).
When the inverter is installed outside, make sure that it
has a clearance of at least 500 mm from the ground
(protection from damage caused by animals).
Installation background
The installation background must meet the following
requirements:
| Temperature-resistant
| Made of flame-retardant material, otherwise use fitting
panel for surfaces at fire risk
| Fixed
| Flat
| Large enough
| Designed for the weight (see chapter 3.7, page 19)
Ambient temperature
| T = 20 to +50 °C
Optimum ambient temperature.
String inverter reaches nominal capacity.
| T = +50 to +60 °C
String inverter output may be reduced (derating).
Operating manual
Voltwerk VS 3, 4, 5