PowPakR | Programming
R
Dimming Module with EcoSystem
041372
Part of the Energi TriPakR Family
Rev. D
08/2014
ALL PROGRAMMING IS OPTIONAL
Programming is not required for default functionality
• Device grouping
• Set a favourite light level
• Set high-end trim for all fixtures
• Set occupancy levels
• Set minimum light level for all fixtures
• Multiple-row daylighting
Please consult individual component installation and
programming
guides for more details.
Set a favorite light level
6
(Optional)
For Pico
wireless controls with a Preset button
®
A
Adjust lights to desired level:
Use the Raise/Lower buttons "
/
"
on the Pico
wireless control.
®
B
Save favorite level:
Press and hold the " Preset " button for
6 seconds.
Set high-end trim for all fixtures
7
(Optional)
Setting High-End Trim:
Lighting electricity usage can be reduced
by 20% or more through high-end trim,
which sets the maximum light level for
each space.
For example, the human eye can barely
distinguish between a 100% and an 80%
light level—setting lights to 80% reduces
energy use by about 20%.
For best results, minimize the amount of sunlight entering the room
before performing the following procedure.
A
Enter trim adjustment mode:
Press & hold the Raise "
" button for
12 seconds.
Lights will flash high-low-high and top LED will be
lit solid.
B
Adjust the high-end trim:
Use the Raise/Lower buttons "
/ "
to adjust and set the lights to the desired
high-end. (50 to 100%)
C
Save the high-end trim:
Press & hold the All On button "
" for
6 seconds to save setting.
Top LED will begin flashing and then turn off to
indicate new level has been saved.
Set minimum light level for all fixtures
8
(Optional)
Certain applications, such as hallways, may require that the
lights never turn off. For these areas, select the 10% option.
A
Enter minimum light level adjustment mode:
Press & hold the Lower button "
" for
12 seconds.
Lights will flash high-low-high and bottom LED will
be lit solid.
B
Adjust the minimum light level:
Press the Raise button " " to set low-end
trim to 10%.
Press the Lower button " " to set low-end
trim to off.
C
Save the minimum light level:
Press & hold the All On button "
" on the
PowPakR Dimming Module for 6 seconds.
Bottom LED will turn off to indicate new level has
been saved.
Device grouping
5
(Optional)
Device grouping allows
Windows
Pico
wireless controls and
®
Radio Powr SavrT Daylight
Sensors to control a group
Daylight
of lights instead of all lights
Sensor
Link
Test
in the room.
Default:
All wireless
transmitters
control all
light fixtures.
Wireless
Enter Grouping
A
B
Press and hold the
" & Raise
All On "
" buttons for
"
6 seconds until the
Clear ConnectR and
EcoSystemR LEDs begin
flashing at a rate
of
second ON
1
2
second OFF.
1
2
Link
Cal.
Test
First fixture will flash.
Note: Occupancy Sensors cannot be
grouped and will control all fixtures.
Set occupancy light levels
9
(Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
A
Set desired occupancy light levels:
Use the Raise/Lower "
/ " buttons on the PowPakR Dimming Module or the Raise/Lower buttons
" on an associated PicoR wireless control(s).
"
/
Note: If certain lights should be unaffected by occupancy, turn lights off using
PicoR wireless control(s).
B
Save occupancy light levels:
Press and hold the " Test " button for 6 seconds on any associated Radio Powr SavrT Occupancy
Sensor. Release when Sensor lens starts to flash.
* If no
button, hold
button.
" Test "
"
Lights On
"
Multiple-row daylighting
10
(Optional)
T
Radio Powr Savr
Daylight Sensor
Sensor must be grouped (Step 5)
Group sensor with ballasts before
beginning multiple-row daylighting.
Link
Cal.
Test
R
R
PowPak
Pico
Wireless
Control
Dimming Module
Raise
All On
Lower
Need Help? www.lutron.com or call the Lutron
Private office or small room
Grouping NOT required.
In small rooms such as private offices,
all lights should respond together and
grouping is not required.
R
PowPak
Dimming
For more information:
Module
www.lutron.com/powpakdimming
Pico
®
Control
Start Grouping
Assign Fixtures
C
Assign / Unassign
Hold
Tap
the Lights
the Lights On
button " d "
Off button
" g " for
6 seconds
Hold
the " Link "
button for
Link
k
Cal.
6 seconds
Test
Test
Assigned: Bright
Unassigned: Dim
*
Press and hold the All On "
A
PowPakR Dimming Module for 6 seconds. Fixtures not controlled by
the Daylight Sensor will go to OFF, all others will go to low end. (First
ballast will begin to flash.)
Press the Raise button " " on PowPakR Dimming Module, or the
B
Lights On button "
" of any associated PicoR wireless control to
toggle the fixture from Window Row (low-end) to Inside Row
(high-end), or vice versa.
Press the Lower button " " on PowPakR Dimming Module, or the
C
Lights Off button "
" on any associated PicoR wireless control to
move to the next fixture. (Next fixture will flash.)
Repeat steps B and C until all rows have been properly set up.
D
Press and hold the All On button "
E
Module, or the " Preset " button on any associated PicoR wireless
control for 6 seconds. (Window Row will begin to flash.)
Lights On
Using the Raise/Lower buttons "
Raise
F
Module or the Raise/Lower buttons "
Preset
wireless control set the current row to your desired light level.
Lower
Tap the All On button "
" on the PowPakR Dimming Module or the
Lights Off
G
Lights Off button "
" on any associated PicoR wireless control to
move to the next row.
Repeat steps F and G until both rows are properly set up.
H
Press and hold the " Cal. " button on the daylight sensor to calibrate
I
room. See step 4 of "Daylight calibration" on reverse.
Technical Support Center at 1.800.523.9466
®
Windows
WINDOW ROW
R
PowPak
Link
Test
Dimming
Daylight
Sensor
Module
INSIDE ROW
Pico
®
Wireless
Controls
Repeat until all fixtures have
Save Grouping
D
been assigned / unassigned
Next Fixture
Tap the
Lights Off
button " g "
Tap the
Tap the
" Cal. "
" Link "
button
button
Link
Link
Test
All fixtures will flash.
Selected fixture will flash.
This will save current group.
Repeat B-D for other
wireless transmitters.
FCC/IC Information:
This device complies with part 15 of the FCC Rules and Industry Canada license-
exempt RSS standard(s). Operation is subject to the following two
conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause
undesired operation.
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the
user's authority to operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur
in a particular installation. If this equipment does cause harmful interference to radio
or television reception, which can be determined by turning the equipment off and on,
the user is encouraged to try to correct the interference by one or more of the following
measures:
" and Lower "
" buttons on the
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in
materials or manufacture within one year after purchase. For warranty
service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd.,
Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of
merchantability is limited to one year from purchase. This warranty does not cover
the cost of installation, removal or reinstallation, or damage resulting from misuse,
abuse, or damage from improper wiring or installation. This warranty does not cover
incidental or consequential damages.
" on PowPakR Dimming
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING
OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE,
INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED
THE PURCHASE PRICE OF THE UNIT.
/ " on the PowPakR Dimming
This warranty gives you specific legal rights, and you may have other rights which vary
" on an associated PicoR
/
from state to state. Some states do not allow the exclusion or
limitation of incidental or consequential damages, or limitation on how long
an implied warranty may last, so the above limitations may not apply to you.
Lutron, Pico, PowPak, Energi TriPak, EcoSystem, Hi-lume, Clear Connect, and
are registered trademarks and Radio Powr Savr is a trademark of
Lutron Electronics Co., Inc.
©2014 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg PA, 18036-1299, USA
Large office or classroom
Radio Powr
Grouping RECOMMENDED.
T
Savr
In large rooms such as conference rooms
Occupancy
Sensor
or classrooms, separate control of some
fixtures, such as whiteboard lights or
daylighting rows, is beneficial. Grouping
is recommended.
For more information:
www.lutron.com/powpakdimming
Exit Grouping
E
Press and hold the All On
" & Raise " " buttons
"
on the PowPakR Dimming
Hold the
Module for 6 seconds until
Lights Off
the LEDs stop flashing.
button
" g " for
6 seconds