BL ON: Backlight always on. When set the backlight will not
automatically turn off after 20 seconds of inactivity.
D V: Battery voltage display. Determines if the battery voltage is
available in the monitoring menu.
D I:
Current display. Determines if the current is available in the
monitoring menu.
D CE: Consumed energy display. Determines if the consumed
energy is available in the monitoring menu.
D SOC: State-of-charge display. Determines if the state-of-charge is
available in the monitoring menu.
D TTG: Time-to-go display. Determines if the time-to-go is available in
the monitoring menu.
ZERO: Zero current calibration. If the BMV reads a non-zero current
even when there is no load and the battery is not charging, this
option can be used to calibrate the zero reading. Ensure that
there really is no current flowing into or out of the battery, then
hold the select button for 3 seconds.
SYNC: Manual synchronization. This option can be used to manually
synchronise the BMV. Refer to chapter 2.3.4 for more
information.
R DEF: Reset to factory defaults. Reset all settings to the factory
defaults by holding the select button for 3 seconds.
Cl HIS: Clear historic data. Clear all historical data by holding the
select button for 5 seconds.
Lock: Setup lock. When on, all settings (except this one) are locked
and cannot be altered.
SW: Firmware version (cannot be altered).
BMV-602S ONLY
AlS: Alarm low starter battery voltage. When the starter battery
voltage falls below this value for more than 10 seconds the low
starter battery voltage alarm is turned on.
AlSc: Clear low starter battery voltage alarm. When the starter battery
voltage rises above this value, the alarm is turned off. This value
needs to be greater than or equal to AlS.
AhS: Alarm high starter battery voltage. When the starter battery
voltage rises above this value for more than 10 seconds the high
starter battery voltage alarm is turned on.
13