SMA Solar Technology AG
5 Technical Data
5.1 Specifications
Parameter
AC
Nominal apparent power
2)
Nominal active power
1)
Reactive power range
Nominal AC voltage
Supported grounding systems
Nominal AC current
Max. AC current
AC total harmonic distortion
(THD at nominal output power)
Power factor – standard
Displacement power factor
Stand-by power consumption
(for communication)
Nominal grid frequency (range)
DC
Max. PV array power
Input voltage range
(at 400 Vac / at 480 Vac)
Nominal voltage DC
(at 400 Vac / at 480 Vac)
MPP voltage range
(at 400 Vac / at 480 Vac)
Startup voltage
(at 400 Vac / at 480 Vac)
Max. input voltage
Min. power on the grid
Max. input current / max.
short-circuit current
Number of independent MPP inputs
/ strings per MPP input
Surge categories
Installation Guide
1)
0 to 75000 var
3 / grounding conductor;
3 x 109 A (at 400 Vac)
> 0.99 at nominal power
0 overexcited to 0 underexcited
50 Hz/60 Hz (± 10%)
565 V to 1000 V / 680 V to 1000 V
630 V / 710 V
570 V to 800 V / 685 V to 800 V
600 V / 720 V
140 A / 210 A
1/1 (split up by external PV array
AC: Surge category III
PV: Surge category II (SC II)
SHP 75-10
75000 VA
75000 W
400 V (50 Hz)
TT, TN
3 x 109 A
< 3%
< 3 W
112500 W
1,000 V
100 W
junction box)
(SC III),
5 Technical Data
STP 60-10
60000 VA
60000 W
0 to 60000 var
3 / grounding conductor;
400 V (50 Hz)
TT, TN
3 x 87 A
3 x 87 A (at 400 Vac)
< 3%
> 0.99 at nominal power
0 overexcited to 0 underexcited
< 3 W
50 Hz/60 Hz (± 10%)
90000 W
565 V to 1000 V / 680 V to 1000 V
630 V / 710 V
570 V to 800 V / 685 V to 800 V
600 V / 720 V
1,000 V
100 W
110 A / 150A
1/1 (split up by external PV array
junction box)
AC: Surge category III
(SC III),
PV: Surge category II (SC II)
SHP75-10-STP60-10-IA-xx-18
41