• Finding Grounded Side of Line
(neutral)
Hold one test prod to the ground and touch
the other test prod to each of the line terminals
until one is found that does not give a voltage
indication. This is the grounded side of the
line.
The continuity LED should also light.
(61-080, 61-076)
• Checking Continuity of Cords, Motors,
Appliances, etc.
Remove power source and place tester across
circuit to be tested. Continuity LED lights if
resistance is less than 500kΩ.
• Locating Excessive Leakage to Ground
(61-080, 61-076)
Place tester across the neutral terminal and the
ground. The single continuity LED should indi-
cate neutral and ground are connected. If both
LEDs light, there is > 5VAC (N-G) indicating a
high resistance leakage to ground.
Battery Replacement
• Replace batteries when touching the leads
together no longer lights the continuity LED.
• Remove test leads from tester.
• Carefully, pry the two battery caps from the
bottom of the case using a screwdriver.
• Replace the batteries.
• Snap the battery caps back in place ensuring
the cap is flush with the bottom of the case.
Accessories:
• 61-070 Standard test leads
• 61-072 Resistor-fused test leads
• C-90 Soft-sided carrying case
• 61-010 Leather case
Maintenance:
• Clean the case with a damp cloth and mild
detergent. Do not use abrasives or solvents.
5
(61-080, 61-076)
(61-080, 61-076)
(61-076, 61-065)
:
(61-080, 61-067)