Technical Specifications - Siemens SIMATIC ET200PRO PS Instrucciones De Uso

Ocultar thumbs Ver también para SIMATIC ET200PRO PS:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
Installation and assembling:
The installation position is horizontal, but preferably with the outgoing cables at the bottom. When installing the unit, be sure to leave enough free
space to guarantee unhindered convection. The supply voltage must be connected in accordance with VDE 0100 and VDE 0160. A protective device
(fuse) with a rating of max. 30A and an isolating device for disconnecting the power supply must be provided
plant the general specifications of the system ET200pro and the Sitop catalogue KT10.1 are to be taken into account.
!
Danger:
The main switch must be switched off and secured against inadvertant reconnection before starting installation or maintenance work. Plugging and
unplugging of the unit is only permissible after disconnection. If these rules are not observed, contact with live parts or improper use can result in
death or severe personal injury.
Description and construction:
The power supply is a stabilized unit designed for use on a three-phase supply. The relevant DIN/VDE regulations or equivalent local regulations must
be observed during installation.
The unit is fastened to the mounting rail by way of the 4 pre-assembled screws. Alternatively, the 4 screws can be replaced with suitable metric collar
screws M5x50 for installation on a unified thread. Proper sealing can only be achieved by using the following accessories:
For IEC usage:
for X1 SIMATIC ET200pro PS:
for X1 SITOP PSU300P:
for X2 SIMATIC ET200pro PS:
NFPA compatibility (National Fire Protection Association)
Modules of the type as described therein are exclusively approved for installation in industrial machines in accordance with the "Electrical Standard for
Industrial Machinery".
for X1 SIMATIC ET200pro PS
for X1 SITOP PSU300P
for X2 SIMATIC ET200pro PS
for X3

Technical specifications:

Specifications valid for input voltage 400 V AC and ambient temperature +25 °C, unless stated otherwise. Subject to change without prior notice.
Type:
Order no.:
Input:
Rated voltage V
:
in
Voltage range:
Line frequency range:
Current (max.) I
:
in
Starting current inrush:
2
I
t:
Overvoltage protection:
Efficiency γ:
Internal fuse:
Disconnect threshold:
Typ. pre-arcing value:
Recommended fuse:
Output:
Rated voltage V
:
out
Residual ripple/spikes:
Rated output power P
:
out
Maximum output current I
:
out
Base load I
:
A bl
Overvoltage limitation U
:
OV
Excess temperature limitation:
Overcurrent limitation on short-circuit or overload:
rms-value of short-circuit current:
Ambient conditions:
During operation:
Ambient temperature:
Humidity rating:
Transportation and storage:
Ambient temperature:
Humidity rating:
Degree of protection (EN 60529):
Protection class:
Mechanical requirements:
For operation, storage and transport
Signal outputs
Power ok:
Excess temperature:
Safety:
Galvanic isolation primary/secondary:
Transformer:
Electromagnetic compatibility
EMC interference emission:
EMC interference immunity:
Certificates:
Siemens AG Deutschland
22.04.2016
3RK1911-2BE30 (6mm²)
3RK1911-2BE50 (2.5mm²)
3RK1911-2BF10 (4mm²)
61 88 201 1003.xx (AWG10)*
61 88 201 1000.xx / 61 88 201 1002.xx (AWG14)*
61 88 202 1010.xx (AWG10)*
Phoenix-Contact SAC-5P-M12-M12FS
3 AC 380 / 480V
3 AC 340V to 550V
45...66 Hz
NFPA 20A at 30°C; 13,4A at 55°C; IEC 26A
< 40A
2
< 3.5 A
s
internal, with varistors
typ. 88% (400V)
4A time-lag
1500A@500V
approx. 60 A
IEC application
Time-lag fuse max. 30A or motor circuit- breaker
Sirius 3RV2021-4NA10
NFPA application
Time-lag fuse max. 25A
class CC: 3NW1 250 OHG,
class RK5 or class J
24 V DC
-5% ... +3%
200 W
8 A
0 A
33V (latching shutdown; for reconnection, switch off supply voltage and wait 1 minute)
internal
105 - 130% static (automatic restart), approx. 50A dynamic (for approx. 100ms, hiccup mode)
< 10A
EN 60721-3-3, climate category 3K3
-25°C ... +55°C
5% - 95%
EN 60721-3-2, climate category 2K4
-40°C ...+70°C
5% - 95%
IP 67, enclosure type5
I (DIN EN 61140 / VDE 0140 T1)
According to EN 60721-3-3, class 3M6
max. 30V,10 mA (observe polarity)
on, if 21.3V ≤ UA ≤ 29V
on, if maximum temperature of the unit is exceeded
PELV according to EN 60950-1
EN 61558-2-17 (1998)
EN 61000-6-4: 2002 conducted and radiated disturbances
Limiting curve A
Requirements according to EN 61000-3-2 are to be ensured within the system, if required
EN 61000-6-2: 2002
CE, UL 508 (use according to NFPA79)
enclosed blind cap X2
enclosed blind cap for X3
enclosed blind cap for X2:
enclosed blind cap for X3
SIMATIC ET200PRO PS
6ES7 148-4PC00-0HA0
2
s
4/8
.
For the installation of the device in the
3RK1902-0CK00
* www.harting.com
3RK1902-0CK00
SITOP PSU 300P
6EP1 433-2CA00
1A
Time-lag fuse max. 5A or motor circuit- breaker
Sirius 3RV2011-1DA10 (2,2...3,2A)
Time-lag fuse max. 5A
class CC/ 3NW1 50 OHG,
class RK5 or class J
SELV according to EN 60950-1
criterion A
SIMATIC ET200PRO PS
SITOP PSU 300P

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sitop psu 300p6es7 148-4pc00-0ha06ep1 433-2ca00

Tabla de contenido