ELECTRICAL REQUIREMENTS - U.S.A. ONLY
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate and in
conformance with the National Electrical Code, ANSI/ NFPA No. 70-latest edition
and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
The electrical power to the oven branch circuit must be shut off while
line connections are being made.
Do not use an extension cord with this appliance.
Electrical ground is required on this appliance. The free end of the green
wire (the ground wire) must be connected to a suitable ground. This
wire must remain grounded to the oven.
If cold water pipe is interrupted by plastic, non metallic gaskets, union
connections or other insulating materials, DO NOT use for grounding.
DO NOT ground to a gas pipe.
DO NOT have a fuse in the NEUTRAL or GROUNDING circuit. A fuse in
the NEUTRAL or GROUNDING circuit could result in an electrical shock.
Check with a quali ed electrician if you are in doubt as to whether the
appliance is properly grounded.
Failure to do so could result in death, re or electric shock.
The range is not equipped with a power cord. The range can be fitted with a 3 or
4-wire NEMA 10-50 or 14-50 type SRDT or ST (as required) power cord rated at
250 volt AC minimum, 40 amp, with ring terminals or open-end spade terminals with
upturned ends and marked for use with ranges.
•
A UL listed strain relief must be attached to the range to hold the power cord.
•
Do not use an aluminum wire receptacle with copper-wired power cord and plug
(or vice versa). The proper wiring and receptacle is a copper-wired power cord
with a copper-wired receptacle.
•
The electrical outlet should be located so that the power cord is accessible when
the range is in the installed position.
6
WARNING
Electrical Shock Hazard