Auxiliary Load Operation; Remove Pump Lid - Zodiac Jandy Pro Serie Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Jandy Pro Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Page 14
ENGLISH
3.4

Auxiliary Load Operation

Certain pump models are equipped with a terminal
bar that provides user access to a built-in Auxiliary
Load relay contact. This normally-open, dry contact
is activated under certain operating conditions and is
primarily intended to be used to control external devices
that require system water flow for proper functioning,
such as heaters, booster pumps, salt water chlorinators,
etc.
See Figures 9 and 10 for compartment's location details.
An access cover with Phillips-head screw must be
removed before proceeding.
Auxiliary Load Connection Requirements
ELECTRICAL SHOCK HAZARD
Due to the potential risk of fire, electric shock, or
injuries to persons, Zodiac
loads must be installed in accordance with the
National Electrical Code
and safety codes, and the occupational Safety and
Health Act (OSHA). Copies of the NEC may be
ordered from the National Protection Association, 470
Atlantic Ave., Boston, MA 02210, or from your local
government inspection agency.
In Canada, Zodiac Pumps must be installed in
accordance with the Canadian Electrical Code (CEC).
• The Auxiliary Load relay contacts are rated at
230V/11A RMS. Please ensure the requirements
of the equipment to be connected to the Auxiliary
Load do not exceed this rating.
1
2
TP133
TP130
/100
TP127
L1
GFCI-
(Black)
Protected
230V
Power
L2
Source 2
(Red or Black)
Line
(Black)
230V
Earth
Auxiliary
Load
Note: Recommended Wiring Configuration
Figure 11. 230V Auxiliary Load, Separate Power
Source Wiring Diagram
Jandy
Pro Series VS FloPro™ Series Variable-Speed Pump
®
WARNING
®
Pumps and any auxiliary
®
(NEC
®
), all local electrical
L2 L1
F1015
F1014
L1
GFCI-
(Black)
Protected
230V
Power
L2
Source 1
(Red or
Black)
Earth
EXAMPLE ONLY
NOT Representative of
all wiring configurations
1
2
TP133
TP130
/100
TP127
Line
GFCI-
(Black)
Protected
115V
Power
Neutral
Source
(White)
(Black)
115V
Earth
Auxiliary
Load
Figure 12. 115V Auxiliary Load, Separate Power
Sources Wiring Diagram
Auxiliary Load Operation Characteristics
Auxiliary Load relay contact activation is speed-
dependent, and behaves as follows:
Contact Closure
From a stopped condition, there is a three-minute delay
before the Auxiliary Load contact is closed when the
motor speed reaches and maintains a speed of at least
1725 RPM.
From a running condition at below 1725 RPM, there is
a five-second delay before the Auxiliary Load contact
is closed when the motor speed reaches and maintains a
speed of at least 1725 RPM.
Contact Opening
If the pump speed is below 1725 RPM, the Auxiliary
Load contact is opened. Contact openings are always
immediate.
3.5

Remove Pump Lid

1.
Make sure that the pump is turned off.
2.
Make sure that the switch to the circuit breaker that
powers the pump motor is turned off.
ELECTRICAL SHOCK HAZARD
Turn off all switches and the main breaker in the variable-
speed pump electrical circuit before starting the procedure.
Failure to comply may cause a shock hazard resulting in
severe personal injury or death.
|
Installation & Operation Manual
L2 L1
F1015
F1014
L1
(Black)
Protected
L2
(Red or
Black)
Earth
Line
EXAMPLE ONLY
NOT Representative of
all wiring configurations
WARNING
GFCI-
230V
Power
Source