13.3.7 Simulation (SIm)
13.3.8 Safety integrity level (SIl)
14 Safe parameterisation - user responsibility
14.1
Safety-related configuration parameters
14.1.1 Common parameters
Name
iN.tYPe
i.RaNGe
V.RaNGe
seNsoR
9116 UNiVeRsal coNVeRteR
it is possible to override the actual measured input signal by a simulated
value. in the Rel.siM menu it is posible to simulate the relay state with out
affecting the analogue output, by pressing
or disconnecting the 4501 device, will disable the simulation mode and bring
the output back to correspond to the actual measured value. simulation is
not possible in sil-mode.
see section 14 - safe parameterisation - user responsibility
Function
selected input type:
teMP = temperature
cURR = current
Volt = Voltage
liN.R = linear resistance
PotM = Potentiometer
selected fixed input range for current measurements (for
iN.tYPe = cURR):
0_20 = 0...20 ma (no sensor error detection!)
4_20 = 4...20 ma
selected fixed input range for voltage measurements
(for iN.tYPe = Volt)
selected temperature sensor type (for iN.tYPe = teMP):
tc = thermocouple
Ni = Ni RtD sensor
Pt = Pt RtD sensor
Version No. V2R0
1
. leaving the simulation menus,
safety Manual
11