14.2.1 If no password is set

1
2
3
4
5
6
7
8
9
10
11
12
13
14
9116 UNiVeRsal coNVeRteR
action
Press oK
set (aDV.set) to Yes and press oK
set setUP to sil and press oK
set eN.sil to Yes and press oK
set password to a number between 0 and
9999 and press oK
(at this time the device starts operating
in sil mode with the entered configuration
parameters!)
Press oK to confirm verification of the oPeN-
>locK in the display
Verify input type and press oK
Verify fixed input current range and press oK
(oNlY if iN.tYPe = cURR)
Verify sensor connection type and press oK
(oNlY if iN.tYPe = teMP and seNsoR = Ni or Pt
or iN.tYPe = liN.R)
Verify temperature unit and press oK
(oNlY if iN.tYPe = teMP)
Verify temperature sensor type and press oK
( oNlY if iN.tYPe = teMP)
Verify Pt sensor type and press oK
(oNlY if iN.tYPe = teMP and seNsoR = Pt)
Verify Ni sensor type and press oK
(oNlY if iN.tYPe = teMP and seNsoR = Ni)
Verify thermocouple type and press oK
(oNlY if iN.tYPe = teMP and seNsoR = tc)
Note 7 : open is shown briefly in the display.
Version No. V2R0
Display shows
aDV.set
setUP
eN.sil
NeW.Pas
coNFiG
Verify
oPeN->locK
(Note 7 )
iN.tYPe
i.RaNGe
coNNec
UNit
seNsoR
Pt.tYPe
Ni.tYPe
tc.tYPe
cJc
safety Manual
17