Parameters Related To Analouge Output - PR electronics 9116-002 Manual De Instrucciones

Convertidor universal
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

eRR.act
oN.Del
oFF.Del
Note 3 : Value not allowed if the relay is used in a safety application (eN.sil =
Yes) and iN.tYPe = cUR and loop supply is used to supply a current input signal.
Note 4 : error detection is enabled if oUt.eRR ≠ none, but relay state at sensor
erroris undefined.

14.1.3. Parameters related to analouge output

Name
o.RaNGe
oUt.eRR
9116 UNiVeRsal coNVeRteR
Relay sensor error action (for Rel.FUN = setP, WiND or eRR):
only relevant if iN.tYPe = teMP, cURR and i.RaNGe = 4-20,
PotM or liN.R and R 0% is ≥ 18.
NoNe (Note 3 ) = sensor error detection Not enabled (Note 4 ),
relay state at sensor error is undefined. (Not for Rel.FUN =
eRR)
oPeN = Relay contact is open at sensor error
clos = Relay contact is closed at sensor error
HolD (Note 3 ) = Relay contact holds the state as before sensor
error occurred. (Not for Rel.FUN = eRR)
Relay oN delay from setP or setP.lo/Hi is crossed in units of
seconds (for Rel.FUN = setP or WiND)
Relay oFF delay from setP +/- HYst or setP.lo/Hi +/- HYst
is crossed in units of seconds (for Rel.FUN = setP or WiND)
Function
Fixed output range for current output:
0-20 = 0...20 ma
Value not allowed when eN.sil = Yes (safety applications)
4-20 = 4...20 ma
20-0 = 20...0 ma
Value not allowed when eN.sil = Yes (safety applications)
20-4 = 20...4 ma
Fixed output value on detected sensor error:
NoNe (Note 5 ) = sensor error detection Not enabled (Note 6 ),
output at sensor error is undefined.
the end user must ensure that the applied sensor including
wiring has a failure rate qualifying it for the safety application
without the detection enabled.
0 ma = output is 0 ma at sensor error
3.5 ma = output is 3.5 ma at sensor error (Ne43 downscale)
23 ma = output is 23 ma at sensor error (Ne4 upscale)
Version No. V2R0
safety Manual
15

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

9116

Tabla de contenido