Ecoflam MAX GAS 350 PR Serie Manual De Uso página 23

Ocultar thumbs Ver también para MAX GAS 350 PR Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 69
Service
­ Maintenance
13
16
Fan assembly
Observe the positioning diagram above
when replacing the motor and blower
wheel. The inside flange A of the blower
wheel must be fitted at the same level as
the equipment plate B. Insert a straight
edge between the wing of the blower wheel
and set A and B to the same height, tighten
the set screw on the blower wheel
(maintenance position 1).
420010594100
14
15
Maintenance on the burner
• Check gas supply components (tubes,
lines) and their connections for leaks
or signs of wear, replace if necessary.
• Check electrical connections and
connection cables for damage,
replace if necessary.
• Check gas filter, clean or replace as
necessary.
• Clean fan wheel and housing and
check for damage.
• Check and clean the mixing unit.
• Check ignition electrodes block,
readjust or replace as necessary.
• Start burner, check flue gas data,
correct burner settings if necessary.
• Check the setting for air pressure
switch and gas pressostat.
• Check the gas train settings.
• Carry out an operating check.
A
A
www.ecoflam­burners.com
EN
23

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max gas 500 pr serieMax gas 350 pr-md tc gn sgt tw 230-50Max gas 350 pr-md tl gn sgt tw 230-50Max gas 500 pr-md tc gn sgt tw 400-50Max gas 500 pr-md tl gn sgt tw 400-503140047 ... Mostrar todo

Tabla de contenido