Technical data

5
Technical data
Note!
The following values apply for all systems:
Permissible flow temperature:
Permissible ambient temperature:
Permissible operating gauge pressure:
Separation level, dissolved gases:
Separation level, free gases:
Degree of protection:
5.1

Electrical system

Type
Power output
Mini
5.2

Dimensions and connections

Type
Weight
Mini
5.3

Operation

Type
System volume
Mini
6

Installation

DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
Ensure that the system is voltage-free before installing the device.
Ensure that the system is secured and cannot be reactivated by other persons.
Ensure that installation work for the electric connection of the device is carried out by an electrician, and in compliance with electrical
engineering regulations.
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there is a risk of burns and other injuries at the connection points, if
pressurised hot water or hot steam suddenly escapes.
Ensure proper installation, removal or maintenance work.
Ensure that the system is de-pressurised before performing installation, removal or maintenance work at the connection points.
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
Wear protective gloves.
Please place appropriate warning signs in the vicinity of the device.
10 — English
Power supply
(W)
(V / Hz)
60
230 / 50
Height
(kg)
(mm)
5.6
420
Working pressure
(m
3
)
1
Servitec Mini — 01.08.2017 - Rev. B
60 °C
0 °C - 45 °C
4.0 bar
≤ 90 %
100 %
IP 54
Electrical current
Electrical voltage control
consumption
(A)
0.3
Width
(mm)
295
Permissible operating gauge
(bar)
0.5-2.5
unit
(V)
230
Depth
(mm)
220
Max. permissible
pressure
operating temperature
(bar)
4
Noise level
(dB)
55
Connection
(inches)
1/2
(°C)
60