DIP-SWITCHES
n°1
ON:
after opening, the gate automatically closes when the delay set on the T.C.A. trimmer
expires.
OFF:
automatic closing disabled.
n°2
ON:
with automatic closing enabled, a sequence of open/close commands causes the gate
to OPENCLOSE-OPEN-CLOSE etc.
OFF: in the same conditions, the same command sequence causes the gate to OPEN-
STOP-CLOSESTOP-OPEN-STOP (step-by-step).
n°3
ON:
(no reverse) during opening the gate ignores any closing commands.
OFF:
the gate's behavior depends on the position of dip switch No.2.
n°4
with software version 1.04 and previous versions
ON:
the deceleration function is on (for motors with limit switch only).
OFF: the deceleration function is off.
with software version 1.05 ÷ 3.00, see table 1.
with software version 3.10 onwards, see table 2.
n°5
ON:
preflashing enabled, each time the gate is operated the light starts flashing 3 seconds
before the gate begins to move.
OFF: when the gate is started, it will move immediately.
n°6
ON:
monostable function of the CH2 control relay (terminals 9 and 10) enabled.
OFF: bistable (or STEP-BY-STEP) function of the CH2 control relay (terminals 9 and 10)
enabled.
n°7
ON:
with dip-switch 6 ON (monostable function), the N.O. contact remains closed for 180
secs. (fixed invariable delay for the timed control of the lights).
OFF: with dip-switch 6 ON (monostable function), the N.O. contact remains closed for 2
secs. (fixed invariable delay for commanding a second automatic system).
with software version 3.10 onwards:
n°6 OFF and n°7 OFF:
n°8
with software version 1.04 and previous versions
not used.
with software version 1.05 ÷ 3.00:
ON:
encoder enabled (see table 1)
OFF: encoder disabled.
with software version 3.10 onwards:
ON:
encoder enabled (see table 2)
OFF: encoder disabled.
n°9
ON:
pressure-sensitive edge on.
OFF: pressure-sensitive edge off.
n°10
ON:
internal push-button panel off. The OPEN/CLOSE and STOP buttons on the lid of the
automation are off. Therefore it is not necessary to short circuit the terminals.
OFF: internal push-button panel on. The OPEN/CLOSE and STOP buttons on the lid of the
automation are on.
IMPORTANT:
Each pair of terminals attached to an NC contact that is not in use must be short-circuited in order to
ensure the proper operation of the board.
The input related to the pressure-sensitive edge must not be short circuited. The device is turned off
by setting dip 9 to OFF.
The door's earthing system must comply with current standards. The manufacturer will accept no li-
ability for any damage deriving from failure to comply with this requirement.
Gate open contact: the contact activates on gate opening, remains active
during the opening time, during the TCA and during closure again. It is
deactivated once the gate has completed closure.