Control CC-R Plus+ Continuous terminal TC-R PLUS

Control CC-R plus + Continuous thermostat terminal TC-R plus

serial connection for wall-mounted remote
-AB+
control (respect the AB polarisation)
H2**
hot water temperature probe 10 kΩ
M1
fan motor DC inverter
S1
grill safety micro-switch
hot water solenoid valve (230V/50Hz 1A
Y1
powered output)
230V/50Hz electrical power supply
L-N
connection
boiler go-ahead output (free contact max
BO
1A)
chiller go-ahead output (free contact max
CH
1A)
Connect as an alternative to the air probe of
*
the wall-mounted control panel
**
If after powering the equipment the board
detects the probe, the start-up will take
place under normal conditions with minimum
water temperature in heating (30 °C) and
maximum water temperature in cooling (20
°C) functions .
The board can also operate without a water
probe, case in which the fan stop thresholds
will be ignored
The 4 spring terminals (ref . A) intended for the
connection of the
wall-mounted TC-R Plus control
panel are compatible with 0 .2 to 1 .5 mm² section (0 .75
mm² if connecting 2 conductors to the same terminal)
rigid or flexible cables, while if they are provided with
lugs with plastic collar, their maximum section should
INSTALLATION
WIRING DIAGRAMS
be of 0 .75 mm² .
Strip the cable by 8 mm and then if the cable is rigid
you should be able to insert it easily while if it is flexible
you will need to use some nose pliers .
Insert the cables completely and make sure they are
properly fixed by pulling them slightly .
8mm
A
To disconnect the cables use a
screwdriver to press the corresponding
white notch (ref .A) and remove the
conductor
Fig .1
2
0.2-1.5mm
9
23