Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Dimensions
• Box 90x90X130 mm included terminal blocks.
• Front panel 96X96 mm.
• Weight 0,6 Kg.
Power Supply
• Power supply (24÷240) Volt AC/DC ± 10% 50/60 Hz without polarity respect,
maximum absorption 4 VA.
Inputs
• Eight analogical inputs, temperature control and mapping with PT100 sensor at
three wires inside range from -10 °C to +200 °C.
Outputs
• Four relays 250V AC, 10 A max (resistive load),one free switch contact.
• ME100: Serial communication port RS485 Full Duplex, own ASCII
communication protocol.
• ME100 V3: Serial communication port RS485 Full Duplex, MODBUS – RTU
communication protocol.
Characteristics
• Self-extinguishable NORYL Box.
• Protection degree front panel in polycarbonate: IP65 (IP66 on request)
• Protection degree of rear panel on terminal board side: IP20
• Display with light segments.
• Visualisation of max temperature and the relevant channel in the automatic
mode.
• Alerts of pre-alarm, alarm, probes fault, fanning, manual function, historic highs.
• System programming directly by frontal panel.
• Possibility to select independently each channel.
• Limit of alarm and pre-alarm settable in the range (-9°C ÷ 199°C).
• Precision ± 1% on full scale ± 1 digit.
• Management of the cooling fan on all channels.

TECHNICAL FEATURES