Dimensions
• Box 90x90X130 mm included terminal blocks.
• Front panel 96X96 mm.
• Weight 0,6 Kg.
Power Supply
• Power supply (24÷240) Volt AC/DC ± 10% 50/60 Hz without polarity respect,
absorption 4 VA.
Inputs
• Eight analogical inputs, temperature control and mapping with PT100 sensor at
three wires inside range from -10 °C to +200 °C.
Outputs
• Five relays 250V AC, 5A max (resistive load), free switch contact.
• Galvanically insulated analogical output 4-20mA referred to the channel with the
most high temperature.
Characteristics
• Self-extinguishable NORYL Box.
• Display with light segments.
• Visualisation of max temperature and the relevant channel in the automatic mode.
• Alerts of pre-alarm, alarm, probes fault, fanning, manual function, historic highs.
• System programming directly by frontal panel.
• Possibility to select independently each channel.
• Limit of alarm and pre-alarm settable in the range (-9°C ÷ 199°C).
• Precision ± 1% on full scale ± 1 digit.
• Cooling fan control on three or four channels.
• Comparison of temperature for cooling fan between two different levels (L and H).
• Four selectable operating modes.
• Detection of fault probes, maximum flexibility of managing and semplicity of
programming, checking of validity of the insert data during programming phase.
TECHNICAL FEATURES
-
-
11
ENGLISH