Conditioners, additives, inhibitors and antifreeze liquids can be used only and
exclusively if the producer guarantees their suitability for use in heating sys-
tems and that they do not cause damage to the boiler's heat exchanger or other
components and/or materials of the boiler and system. The use of generic
chemicals not specific for use in heating systems and/or incompatible with the
materials of the boiler and system is forbidden. Chemical conditioners must en-
sure complete deoxygenation of the water, must contain specific protection for
yellow metals (copper and its alloys), anti-fouling agents for scale at least up to
15°F, neutral pH stabilizers and, in low-temperature systems, specific biocides
for use in heating systems.
B
The unit is equipped with an antifreeze system that activates the boiler in heat-
ing mode when the system delivery water temperature drops below 6 °C. The
device is not active if the power and/or gas supply to the unit is turned off.
If necessary, for system protection use a suitable antifreeze liquid that meets
the same requirements as set out above and provided for by Standard UNI
8065.
B
Regarding domestic hot water, no type of treatment that can prevent its possi-
ble food use can be provided for.
Plumbing circuit examples
In the examples described below the checking/change of some parameters may be re-
quired.
To do this it is necessary to access the Technician menu.
From the main screen (Home), press the main Menu button (detail 12 - fig. 1).
Access the "Technician" menu by pressing the contextual button 2 (detail 2 - fig. 1).
MENU
USER
TECHNICIAN
Enter the code "4 1 8" with contextual buttons 1 and 2. Confirm each number with the
OK button.
Technician menu
Insert code:
0
X X
to select
to confirm
Access the Parameters menu by pressing the OK button.
PARAMETERS MODE
to confirm
2
fig. 33
1
2
fig. 34
1
2
fig. 35
cod. 3541F572 - Rev. 01 - 09/2015
Access the "Configuration Menu" or "System Type Menu" according to the parameter to
be modified as given in each water circuit example.
Configuration Menu
b
P
to confirm
12
Type Menu
P .
P .
b
o
P
o
to confirm
fig. 36
EN
9