Chassis Installation

STEP1 Slide the chassis into the cabinet stopping approximately 3" from full insertion. Stuff the chassis seal gasket (Item
#12) one inch deep between the chassis and the cabinet (Figure 36). Begin at either bottom corner and go up the side, across
the top, and down the opposite side. Make sure that the gasket is behind the conduit connector (furthest from you). Push the
chassis into the shell the remaining distance so that the plastic front shrouds the front edge of the shell. Fasten the junction
box mounting foot to the shell with the sheet metal screw.
If chassis seal gasket is not installed, the operation of the unit will be negatively affected. Also, the operation noise and outside
noise will be amplified.
CAUTION
Excessive Weight Hazard
Usetwo or more people when
installing your air conditioner.
Failure to do socan result in
backor other injury.
NOTE:
Field wiring must be provided to this junction box in accordance with NATIONAL ELECTRIC CODE (NFPA 70, 2008 or current
edition) ARTICLE 501. Field and equipment grounds are to be terminated at the post in the junction box with the green screw
provided. Equipment power leads are to be connected with the field supply by means of wire nuts (not provided). Install the
gasket and cover plate onto the junction box.
Figure 36
CHASSIS SEAL GASKET
CAUTION
Cut/Sever
Although great care has been
taken to minimize sharp edges
in the construction of your unit,
use gloves or other hand
protection when handling unit.
Failure to do socan result in minor
to moderate personal injury.
WARNING
Explosion Hazard
Electrical Shock Hazard
Electrically connect unit in accordance with NEC
Code Article 501. Failure to do so can result in
death, explosion, fire, or electrical shock.