Press DATA-ENTER to confirm the selected value – CO-40 appears on display.
Press RUN on the programmer.
Turn the main door switch off and on again and perform an operation check
Circuit board wiring diagram with Remote control operating mode
- 6 - CONTROL MODE – (DEAD-MAN CONTROL IN OPENING ONLY )-
USE: The door only opens if the open pushbutton (HELP) is pressed and held. It stops as soon as the pushbutton is released.
Maximum opening is as set in CO-02.
Closing is controlled by pushbutton SYS pressed briefly.
Therefore panels with both pushbuttons are required or alternatively keyswitches or other device capable of supplying both single pulse or permanent
commands.
When open, the door does not close again if the opening command is still engaged.
During closing, if the photocells connected to LIMIT are engaged, closing is stopped and the door only resumes movement when the photocells are
freed.
If the D/N switch (DAY/NIGHT function) is set to DAY (closed contact), the electric lock is permanently released; if set to NIGHT (open contact) the
electric lock is enabled.
Circuit board connections: Connect the open control to wires 5-7 (0-HELP) and closing to wires 5-6 (0-SYS).
Set one or 2 photocell pairs and connect to wires 4-5 (0-LIMIT).
An emergency pushbutton can be fitted by connecting it to wires 8-9 (0-STOP).
A switch/selector should also be connected to wires 3-5 (-0V-D/N) to enable selection of the day/night mode.
N.B. INSIDE AND OUTSIDE INPUTS IN THIS CONFIGURATION ARE NOT ENABLED
Programmer parameter setting procedure
Turn on the power supply
Press STOP on the programmer
Press DATA-ENTER - "CO-00" appears on display
Press the up key once - "CO-01" is displayed
Press DATA-ENTER on CO-01 to enter the Options menu
Select option "6" by means of the up/down keys.
Press DATA-ENTER to confirm the selection – "CO-02" appears on display.
Press DATA-ENTER on CO-02.
Set the opening width (max. opening) by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected width – CO-03 appears on display.
Press the up key until CO-39 is displayed
Press DATA-ENTER on CO-39.
Enter the door weight by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected value – CO-40 appears on display.
Press RUN on the programmer.
Turn the main door switch off and on again and perform an operation check
- 7 - THREE-STOP MODE -
USE: 3 different opening widths can be activated; maximum on CO-02, medium on CO-20, and minimum on C0-21.
During closing, if sensors or control pushbuttons are engaged, opening width will be equal to the distance set for closing.
If the D/N switch (DAY/NIGHT function) is set to DAY (closed contact), the electric lock is permanently released; if set to NIGHT (open contact) the
electric lock is enabled. Wait time before automatic re-closing is set on CO-09.
Circuit board connections: Connect the maximum open control to wires 5-7 (0-HELP), medium opening to wires 5-6 (0-SYS) and minimum opening
to wires 4-5 (0-LIMIT). A switch/selector should also be connected to wires 3-5 (-0V-D/N) to enable selection of the day/night mode
N.B. INSIDE AND OUTSIDE INPUTS IN THIS CONFIGURATION ARE NOT ENABLED (however, sensors can be connected to the HELP, SYS or
LIMIT for control of the different opening modes. If enabled, these controls stop the door during closing and invert direction).