Ecoflam Blu 500 PR Manual De Instrucciones página 17

Quemador de gas progresivos en modulante
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The Landis control box starts the fan and begins the pre-purging of the combustion chamber. The air pressure switch controls the
correct operation. At the end of the pre-purging phase, the ignition transformer cuts-in followed by the opening of the gas valves.
In case of missed ignition or accidental shutdown, the ionisation probe cuts-in and set the burner in lockout mode within the safety
time.
Gas pressure swi ch
Mo or
Air pressure swi ch
Transformer
Gas valve
High flame ON/OFF
Flame de ec ion
Lock ou
SATRONIC DMG 972 CONTROL INFORMATION SYSTEM
The SATRONIC DMG 972 control is a micro-processor control which provides information about the current opera-
tion of the burner and the cause of any faults. The information is available by reading the "flash code" at the red LED
within the lockout reset button as detailed below. By the use of additional monitoring equipment a short history of
recorded faults is also available. There are two types of additional monitoring devices available from Satronic Ltd. The
"satropen" is a small pocket reader designed to give a visual read out of status, flame current and supply voltage.
Computer software is available to allow access to the current information and stored data.
On burner failure the red LED is permanently illuminated for a period of approximately 10 seconds, followed by a
brief "dark phase", then one of the following flash codes will indicate the cause of the fault. This indication will repeate
as long as the lockout reset button is not reset.
Message
Flash-Code
waiting for air proving
switch
pre-purge (tv1)
pre-ignition (tvz)
safety time (ts)
delay 2nd stage (tv2)
running
low mains voltage
Flash-Code Key
short pulse
long pulse
short pause
.
long pause
_
CONTROL BOXES LANDIS & STAEFA LGB22
2
3
1
lamp
FAULT DISPLAY MESSAGES
.
.
.
.
.
_
_
4
Description
1
pressure swi ch con rol ime-ou
2
ime-ou for air pressure confirma ion
5
3
prewashing ime
4
safe y ime
6
5
preigni ion ime
6
ime-ou
Error diagnosis
Error message
Flash-Code
lockout
safety time
air proving switch
in closed position
air proving switch
time-out
air proving switch
opened
loss of flame
Flash-Code for manual lock out
manual/external
lock out
pag.17
LB 381 BLU 500 -1400 PR / MD
o enable fuel 2nd valve
Possible fault
within lock out safety time
no flame establishment
air proving switch
contact welded
air proving switch does not
close within specified time
air proving switch opens
during start or operation
loss of flame during operation
B
9"
3"
30"
3"
3"
8"

Publicidad

Tabla de contenido
loading

Tabla de contenido