B LB 381 BLU 500 -1400 PR / MD
LANDIS & STAEFA SQN 31 251A2700 AIR DAMPER MOTOR
MANUAL RELEASE
SWITCH
1
ADJUSTING THE MAXIMUM CAPACITY OF THE BURNER
Position the selector, situated on the control panel, on position maximum power and proceed as follows:
Adjusting the maximum gas flow rate: - proceed as stated in the regulating the solenoid valves until you achieve the
correct gas flow, as established by analyzing the combustion process. Eventually adjust the gas flow rate using a suitable
allen wrench, alter the position of the cam(3) guide blade; if you screw it down, the flow rate is reduced; if you
unscrew it, the flow rate increases.
Adjusting the maximum air flow rate: Eventually adjust this position acting on the screw "1 ", after loosening nut " 2
".
"2"
Tighten the nut
in place once again
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER
Position the selector, situated on the control panel, on position minimum power and proceed as follows:
Adjusting the minimum gas flow rate: using a suitable Allen wrench, alter the position of the cam(3) guide blade; if
you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
Adjusting the minimum air flow rate: adjust on limit switch for air damper "Low Flame" position adjustment.
ADJUSTING THE INTERMEDIATE BURNER CAPACITIES
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjusting the intermediate gas flow rates: using a suitable Allen wrench, alter the position of the cam(3) guide blade;
if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
Remove cover to gain access to the adjusting cams.The cams are to be adju-
sted through the suitable key provided for. Description:
I
- Limit switch for air damper "High Flame" position adjustment
(Max. power)
II - Limit switch for the air damper position at burner's shut down
III - Limit switch for air damper "Low Flame" position adjustment
(Min. power)
V - Limit switch "NOT USED".

AIR ADJUSTMENT

2
.
pag.18
SELECTOR
AUTO
3
0
0 = operating elements locked
in an intermediate position
= operation on maximum capacity
= operation on minimum capacity
AUTO = automatic operation