Before Test Run - Mitsubishi Electric Mr.SLIM PKA-A12GA Manual De Instalación

Ocultar thumbs Ver también para Mr.SLIM PKA-A12GA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6.
Electrical work
Function
table
Select unit number 00
Mode
Power failure automatic
recovery
Indoor temperature
detecting
Settings
Mode no.
Not available
01
Available
"1
Indoor unit operating average
Set by indoor unit's remote controller
02
Remote controller's
internal sensor
Not Supported
Supported
(indoor unit is not equipped with outdoor-air intake)
03
Supported
(indoor unit is equipped with outdoor-air
intake)
230 V
04
208 V
Energy saving cycle automatically
enabled
05
Energy saving cycle automatically
disabled
Mode no.
O7
LOSSNAY connectivity
Power voltage
Auto mode (only for PUHZ)
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07
[wireless remote controller])
Mode
Settings
Filter sign
100Hr
2500Hr
No filter sign indicator
Standard
(PLA)/Silent
(PCA)
High ceiling _ (PLA)/Standard
(PCA)
High ceiling (_) (PLA)/High
ceiling (PCA)
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup _'})
Equipped with vanes (vanes angle setup @})
Disabled
Enabled
Fan speed
No. of air outlets
Installed options (high-performance
filter)
Up/down vane setting
Energy saving air flow
(Heating
mode)
O8
O9
10
11
12
Setting no.
Initial setting
1
2
O
1
O
2
3
1
O
2
3
1
O
2
1
O
2
Setting no.
Initial setting
1
O
2
3
1
2
3
1
2
3
1
2
1
2
3
1
2
setting
setting
"1 When the power supply
returns, the air conditioner
will start 3 minutes
later.
7. Test run
7.1. Before test run
I_ After completing
installation and thewiring
and piping of the indoor and outdoor
_ Do not carry out this test on the control
wiring
(low voltage
circuit)
termi-
units, check for refrigerant
leakage, looseness in the power supply or control
hale.
wiring, wrong polarity, and no disconnection
of one phase in the supply.
Z_ Warning:
I_ Use a 500-volt megohmmeter
to check that the resistance
between the power
Do not use the air conditioner
if the insulation
resistance
is less than 1.0 M_.
supply
terminals
and ground is at least 1.0 M_.
Insulation
resistance
®@
(D @
Fig. 74
@ ON/OFF
button
_p Test run display
© Indoor temperature
liquid line
temperature
display
@ ON/OFF
lamp
Power display
CF_ Error code display
Test run remaining time dis-
play
Set temperature
button
CH)Mode selection
button
Ci_Fan speed button
@ TEST button
7.2. Test run
The following
3 methods
are available.
7.2.1.
Using
wired
remote
controller
(Fig.
7-1)
(_) Turn on the power at least 12 hours before the test run.
@_ Press the [TEST] button twice. =, "TEST RUN" liquid crystal display
(_) Press the [Mode selection] button. = Make sure that wind is blown out.
@ Press the [Mode selection] button and switch to the cooling (or heating)
mode.
=, Make sure that cold (or warm) wind is blown out.
(_ Press the [Fan speed] button. = Make sure that the wind speed is switched.
(_ Check operation
of the outdoor unit fan.
_'} Release test run by pressing the [ON/OFF] button. _, Stop
(_ Register a telephone number.
The telephone
number of the repair shop, sales office, etc., to contact if an error
occurs can be registered
in the remote controller. The telephone
number will be
displayed when an error occurs. For registration
procedures,
refer to the operation
manual for the indoor unit.
7.2.2.
Using
wireless
remote
controller
(Fig.
7-2)
_} Turn on the power to the unit at least 12 hours before the test run.
@
Press the _
button twice continuously.
(Start this operation from the status of remote controller
display turned off.)
(_) _
and current operation mode are displayed.
(_) Press the [L_
(O O"_, D I;3) button to activate COOLO mode, then check whether
cool air is blown out from the unit.
_} Press the _
(O O'_ _ t_3.) button to activate HEATa mode, then check whether
warm air is blown out from the unit.
FAN
(_) Press the _
button and check whether fan speed changes.
VANE
(_ Press the _
button and check whether the auto vane operates properly.
(_ Press the ON/OFF
button to stop the test run.
12
Fig. 7-2
Note:
o Point the remote controller
towards
the indoor unit receiver while
following
steps (_) to (_).
, It is not possible to run the in FAN, DRY or AUTO mode.

Publicidad