7. Test run
[Output pattern B]
Wireless
remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote
controller
Check code
Symptom
Remark
1
E9
Indoor/outdoor
unit communication
error (Transmitting error) (Outdoor unit)
2
UP
Compressor
overcurrent
interruption
3
U3, U4
Open/short
of outdoor unit thermistors
4
UF
Compressor
overcurrent
interruption
(When compressor
locked)
5
i U2
Abnormal
high discharging
temperature/49C
worked/insufficient
refrigerant
6
i U1, Ud
Abnormal
high pressure
(63H worked)/Overheating
safeguard
operation
7
i U5
Abnormal
temperature
of heat sink
For details, check the LED display
8
i U8
Outdoor unit fan safeguard
stop
of the outdoor controller
board.
9
i U6
Compressor
overcurrent
interruption/Abnormal
of power module
10
i U7
Abnormality
of super heat due to low discharge temperature
11
i U9, UH
Abnormality
such as overvoltage
or voltage shortage and abnormal synchronous
signal to main circuit/Current
sensor error
12
,-
-
13
,-
-
14
Others
Other errors (Refer to the technical
manual for the outdoor unit.)
"1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION
INDICATOR lamp does not come on,
there are no error records.
*2 If the beeper sounds three times continuously
"beep, beep, beep (0.4 4- 0.4 4- 0.4 sec.)" after the initial two beeps to confirm
the self-check
start signal was received, the
specified
refrigerant address
is incorrect.
o On wireless
remote controller
The continuous
buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
On wired remote controller
Check code displayed in the LCD.
If the unit cannot be operated properly after the above test run has been performed,
refer to the following table to remove the cause.
Symptom
Wired remote controller
For about 2
minutes following
power-on
PLEASE WAIT
PLEASE WAIT -_ Error code
After about 2
minutes has
expired following
power-on
Display messages
do not appear even
when operation switch is turned ON
i (operation
lamp does not light up).
LED 1,2 (PCB in outdoor unit)
After LED 1,2 are lighted, LED 2 is turned off,
i then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. -_ LED 1,2 blink.
i Only LED 1 is lighted. -_ LED 1 blinks twice,
i LED 2 blinks once.
phenomena
takes place.
Cause
For about 2 minutes following
power-on,
operation
of the
remote controller is not possible due to system start-up. (Cor-
rect operation)
Connector
for the outdoor unit's protection
device is not con-
nected.
Reverse or open phase wiring for the outdoor unit's power
terminal block (L1, L2, GR)
Incorrect wiring between indoor and outdoor units (incorrect
polarity of Sl, S2, $3)
Remote controller wire short
On the wireless
remote controller
with condition above, followin
No signals from the remote controller
are accepted.
OPE lamp is blinking.
The buzzer makes a short pipng sound.
Note:
Operation
is not possible for about 30 seconds after cancellation
of function
selection.
(Correct
operation)
For description
of each LED (LED 1,2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer)
Indicates whether control power is supplied. Make sure that this LED is always lit.
LED 2 (power for remote controller)
Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected
to the outdoor unit refrigerant
address "0".
LED 3 (communication between indoor and outdoor units only A-control)
Indicates state of communication
between
the indoor and outdoor units. Make sure that this LED is
always blinking.
14