Installation of Indoor, Outdoor Unit

2. Outdoor unit

• If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
• Select a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
3. Piping length and the elevation
Single Operation
Pipe Size
Unit : mm(inch)
Capacity
Gas
42k Btu/h
15.88(5/8)
Indoor unit
A
B
8 Air Conditioner
Liquid
Standard
9.52(3/8)
7.5(25)
Outdoor unit
Indoor unit
More than
300(11.8)
F e
n c
o b
e o
s t a
c l e
Length A
Unit : m(ft)
Max.
50(164)Cassette type
40(131)Floor standing type
Outdoor unit
A
B
r
s
More than 600(23.6)
More than 700(27.6)
Elevation B
Unit : m(ft)
Standard
Max.
30(98)Cassette type
5(16)
25(82)Floor standing type
A
Oil trap
Indoor unit
If piping length is more than 20m(66 ft)
Oil trap should be installed every 10m(33 ft)
More than
More than
300(11.8)
300(11.8)
Unit : mm(inch)
*Additional
refrigerant
Unit : g/m
(oz/ft)
40(0.43)
Outdoor unit
B