CAN Communication Plug-in Module
The location of the DIP-switches for selecting the
type of analog input and output signal and RS485 line
termination can be better visualized in
the analog inputs and/ or outputs with signals in current,
adjust switch S1 and the related parameters according to
table
1. For further details about the control connections
refer to Chapter 3 - Installation and Connection of
CFW500 user's manual.
Table 1: Settings of switches to select the type of analog
input and output signal of the CFW500-CCAN
Input /
Signal
Output
Voltage S1.1 = OFF
AI1
Current
Voltage
AO1
Current S1.2 = OFF
NOTE!
Settings for connection of the RS485:
S1.3 = ON and S1.4 = ON: termination
RS485 ON
S1.3 = OFF and S1.4 = OFF: termination
RS485 OFF
Any other combination of switches is not
allowed.
The CFW500-CCAN Comunication Plug-in Module has
a 5-way plug-in connector for CAN communication with
the following features:
Allows communication CANopen and DeviceNet
in the product.
Galvanically isolated interface fron main power
supply with a differential signal, giving greater
resistance against electromagnetic interference.
allows connection of up to 64 devices on the
same segment. A larger number of devices can be
connected using repeaters. The maximum number
of devices that can be plugged into the network also
depends on the protocol used.
Maximum bus length of 1000 meters.
8 | CFW500
Setting of
Range of
Switch S1
0...20 mA
S1.1 = ON
4...20 mA
S1.2 = ON
0...20 mA
4...20 mA
figure
A.2. To use
Parameters
Signal
Setting
0...10 V
P0233 = 0 or 2
P0233 = 0 or 2
P0233 = 1 or 3
0...10 V
P0253 = 0 or 3
P0253 = 1 or 4
P0253 = 2 or 5