Installation Of Voltage Input Wires - Leviton MDNCT-2SC Manual Del Usuario E Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3
INSTALLATION INSTRUCTIONS
3.8.2

Installation of Voltage Input Wires

1. Depending on the branch circuit, in-line fuses may be required by local
electrical codes.
2. Connect wiring for Line voltages and Neutral to the appropriate locations in the
breaker panel in accordance with all national and local electrical codes; see
Figure 4 for wiring diagram. Table 2 lists the voltage inputs.
3. The power source of the meter must be the same as the power source of the
load that the meter is measuring.
4. Trim the wire to the appropriate length to avoid coils of excess wiring.
5. Strip wiring to 0.3 inch if needed and connect to the appropriate terminals.
Voltage Inputs
L1
L2
N
Description
Voltage Input, Line 1 Black Wire (Required)
Voltage Input, Line 2 Red Wire
Neutral input, White Wire (Required)
Table 2 - Voltage Connections
Note: In-line fuses recommended
Figure 4 - Voltage Wiring Diagram