INSTALLATION INSTRUCTIONS
3.9
Output Connections
The meter's pulse and counter outputs report total real energy consumed. For dual-
element meters, this is a combined total for Line 1 and Line 2. The 10 Wh isolated
output is typically used for meter verification and calibration. The 100 Wh and 1000
Wh isolated outputs are intended for automatic meter reading (AMR) systems. There
are two terminals for mechanical counter connection. There is no polarity associated
with the terminals. V
Output connections are listed in Table 4.
10 (+) Opto-Isolated Output
100 (+) Opto-Isolated Output
1000 (+) Opto-Isolated Output
ISOL COM (-)
COUNTER (+ and -)
1 count = 100 Wh for 0.1kWh models
1 count = 1000 Wh for 1kWh models
+12VDC
CE
Table 4 - Isolated Pulse Output Connections
Total Real Energy (kWh) consumption
(energy delivered) pulse output, plus (+)
connection (connect to signal input). 10Wh
pulse rate (5 watt hours on, 5 watt hours off).
VCE = 40VDC; ICE 50mA max.
Total Real Energy (kWh) consumption
(energy delivered) pulse output, plus (+)
connection (connect to signal input).
100Wh pulse rate (50 watt hours on,
50 watt hours off).
VCE = 40VDC; ICE 50mA max.
Total Real Energy (kWh) consumption
(energy delivered) pulse output, plus (+)
connection (connect to signal input). 1kWh
pulse rate (500 watt hours on, 500 watt
hours off).
VCE = 40VDC; ICE 50mA max.
Common (-) connection for 10Wh, 100Wh
and 1000Wh Isolated Pulse Outputs.
See connection in diagrams above.
For 12 VDC electro-mechanical counter
(not isolated). There is no polarity associated
with the two wires of the counter - either wire
can be connected to the + (pulse) output.
12 VDC @ 10mA output (not isolated) for
specialized applications such as a line
powered transmitter.
Use with COUNTER (-).