Diagnostic Messages; Keypad Lock; Remote Control; Commands Menu - LOVATO ELECTRIC ATL10 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DIAGNOSTIC MESSAGES

– The ATL10 display can show messages to signal the implementation of a function or a particular situation
– By pressing one of the keys for measure selection, the diagnostic display is temporarily stopped to allow to view the measure.
MESSAGES
GENERATOR STARTING
COOLING TIME
LINE FAILURE SIMULATION
---- (Interlock time in progress)

KEYPAD LOCK

KEYPAD UNLOCK
KEYPAD LOCK
– The ATL10 keypad can be locked either by means of a programmable input or with a particular procedure from front keys
– Once the keypad is locked, it will only be possible to view measures, but not to change operating mode or to operate manually on circuit breakers. Only the
keys for measure selection will remain enabled
– Any attempt to use the locked keys will cause the message KEYBOARD LOCKED to be displayed
– To lock or unlock the keypad, press key B and, while holding it down, press key A three times without releasing it at the end
– Release then key B and then press it 5 times, then release both keys
– When the keypad is locked, the display shows the word KEYBOARD LOCKED. Conversely it has been unlocked, the message KEYBOARD UNLOCKED would
appear.

REMOTE CONTROL

– It is possible to connect ATL10 to a PC through its serial interface to access parameter programming and monitor the operation of the device using the
dedicated software ATLSW or using a generic SCADA software that supports Modbus protocol
– ATL10 can be connected directly in peer-to-peer configuration using the RS-232 serial interface port and cable code 51C2.

COMMANDS MENU

With this menu it is possible to execute the following parameters:
– Set the factory default parameters.
– Save a backup copy of user-edited setup parameters.
– Restore the set-up to the values saved in the backup memory.
– To access the commands menu hold D, press A for 2 times then press B for 3 times, press C for 4 times.
– The display will show COMMANDS MENU, wait a few seconds or press the D key to access menus.
– The display shows the code of the first menu C01 and its description.
– Press key A to select the parameter.
– Press E to execute the selected command.
– Press key D to quit commands menu.
– If no keys are pressed for more than 2 minutes, the unit exits menu automatically .
COMMANDS MENU
C01
PARAMETERS TO FACTORY DEFAULT
C02
BACKUP PARAMETRER SET-UP
C03
RESTORE PARAMETER SET-UP
G
B
11

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido