Menu P5 - Programmable Inputs - LOVATO ELECTRIC ATL10 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8
MENU P5 – PROGRAMMABLE INPUTS
PAR
Function
P5.1.1
Prog. input Function 1
terminal 2.1
P5.1.2
Prog. input 1 mode normal/inverted
P5.1.3
Closing delay
P5.1.4
Opening delay
P5.2.1
Prog. input Function 2
terminal 2.2
P5.2.2
Prog. input 2 mode normal/inverted
P5.2.3
Closing delay
P5.2.4
Opening delay
P5.3.1
Prog. input Function 3
terminal 2.3
P5.3.2
Prog. input 3 mode normal/inverted
P5.3.3
Closing delay
P5.3.4
Opening delay
P5.4.1
Prog. input Function 4
terminal 2.4
P5.4.2
Prog. input 4 mode normal/inverted
P5.4.3
Closing delay
P5.4.4
Opening delay
P5.5.1
Prog. input Function 5
terminal 2.5
P5.5.2
Prog. input 5 mode normal/inverted
P5.5.3
Closing delay
P5.5.4
Opening delay
P5.6.1
Prog. input Function 6
terminal 2.6
P5.6.2
Prog. input 6 mode normal/inverted
P5.6.3
Closing delay
P5.6.4
Opening delay
Functions of programmable Inputs
COD
Function
OFF
Input not used
FB.1
Line 1 circuit breaker closed (Feedback 1)
Auxiliary contact informing the ATL10 of the open/closed status of line 1 circuit breaker. If this signal is not connected, ATL10 considers
the status of the circuit breaker corresponding to the status of control outputs
FB.2
Line 2 circuit breaker closed (Feedback 2)
Like Fb.1, referred to line 2
TR.1
Line 1 circuit breaker protection (Trip 1)
When the contact is closed, it generates an alarm of line 1 circuit breaker protection intervention
TR.2
Line 2 circuit breaker protection (Trip 2)
Like tr.1, referred to line 2
E.TR
Transfer to secondary line
When closed, causes changeover to secondary line even if main line voltage is within limits.
It can be used to switch the priority between line 1 and line 2.
The secondary line circuit breaker remains activated until this line remains within limits.
Can be used for EJP function
IN.R
Inhibit Return to main line
In AUT mode, when closed, it inhibits the return to main line after it has reverted to the limit range.
It is used to prevent the second power cutout due to re-transfer from occurring automatically at an unforeseeable time
S.GE
Start Generator
In AUT mode, when closed, it causes the generator to start after the delay specified by P2.20. It can be used for EJP function
EME
Emergency
NC contact which, if open, causes both circuit breakers to open and generates alarm A09
GR.2
Line 2 generator ready (Generator ready 2)
When closed it signals that the generator connected to line 2 is aviable for use. If this signal is missing, allìarm A08 is generated
E.L1
Enable load on line 1 (Enable Load 1)
It allows load connection on line 1, in addition to internal controls
E.L2
Enable load on line 2 (Enable Load 2)
Like EL.1, referred to line 2
LOC
Keypad lock (Lock)
If closed, it locks all the functions from front keypad except measure viewing
L.PA
Lock Parameters
If closed, it locks the access to setup menus
Range
Default
See following list
FB.1
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
See following list
FB.2
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
See following list
TR.1
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
See following list
TR.2
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
See following list
E.TR
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
See following list
IN.R
NOR/INV
NOR
0.0-25.0 s
0.0 s
0.0-25.0 s
0.0 s
G
B

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido