Quick Parameter Reference, Faults and Alarms
Fault / Alarm
A0758
Alarm that indicates the parameter for
Program Indirect
engineering unit of the motor speed
Engineering Unit
was not programmed for Hz or rpm.
4 (P0516) for Hz
or rpm
A0760
Alarm that indicates the process
Low Level of the
variable of the main PID controller has
Process Variable
a low value.
of the Main PID
Controller
A0762
Alarm that indicates the process
High Level in the
variable of the main PID controller has
Process Variable
a high value.
of the Main PID
Controller
A0764
Alarm that indicates the CFW501
Frequency Inverter
frequency inverter is in the sleep mode.
in Sleep Mode
A0766
Alarm that indicates the dry pump
Dry Pump
condition was detected for the pump
Detected
driven by the CFW501 frequency
inverter.
A0768
Alarm that indicates the broken belt
Broken Belt
condition was detected for the motor
Detected
driven by the CFW501 frequency
inverter.
A0770
Alarm that indicates the need of
Filter Maintenance
replacing the system filter.
A0780
Alarm that indicates an analog input
Program AIx for
was not programmed for the process
Process Variable
variable of the external PID controller.
of the External PID
Controller
A0782
Alarm that indicates a digital input was
Program DIx
not programmed for automatic / manual
for Automatic /
selection of the external PID controller.
Manual Selection
of the External PID
Controller
A0784
Alarm that indicates an analog output
Program AOx
was not programmed for output of the
for Output of
external PID controller.
the External PID
Controller
A0786
Alarm that indicates the process
Low Level of the
variable of the external PID controller
Process Variable
has a low value.
of the External PID
Controller
22 | CFW501
Description
Possible Causes
Parameter P0516 was not programmed for 13 (Hz)
or 3 (rpm).
Parameter P1030 is programmed for 1 and the value
of the process variable of the main PID controller
remained below the value programmed in P1031 for
the time programmed in P1032.
Parameter P1030 is programmed for 1 and the value
of the process variable of the main PID controller
remained above the value programmed in P1033 for
the time programmed in P1034.
Main PID controller is enabled and in automatic mode,
and the motor speed remained below the speed
programmed in P1036 for the time programmed
in P1037.
Parameter P1042 is programmed for 1 and the pump
driven by the CFW501 frequency inverter is running
with speed above the speed programmed in P1043
and the motor torque remained below the value
programmed in P1044 for the time programmed
in P1045.
Parameter P1046 is programmed for 1 and the motor
driven by the CFW501 frequency inverter is running
with speed above the speed programmed in P1047
and the motor torque remained below the value
programmed in P1048 for the time programmed
in P1049.
Parameter P1050 is programmed for 1 and the
operation time of the motor driven by the CFW501
frequency inverter shown in P1052 is above the value
programmed in P1051.
Parameter P0231 or P0236 was not programmed
for 8.
Parameter P0263 or P0264 or P0265 or P0266 was
not programmed for 21.
Parameter P0251 or P0254 was not programmed
for 16.
Parameter P1075 is programmed for 1 and the value
of the process variable of the external PID controller
remained below the value programmed in P1076 for
the time programmed in P1077.