Application
The POLYGYR-Ace controlller is used for the control of packaged airconditioning units or heating plant.
Two adigital outputs selectable between 2 stages of on/off control or as a single 3 point controller.
A digital relay contact input is used to select either day/night or summer/winter switch-over as determined by the setting of
the corresponding parameter.
The second analogue input can be used for the following applications:
PI Limiter
Remote Set point
Temperature differential
Temperature shift
The setting of the parameters are displayed on the LCD.
The RWC32/RWC82 controller is intended for either DIN rail mounting in a switchboard or screw mounting for external use.
Parameters
(default values in brackets)
Name
Description
Main
Main temperature
Ts
Temperature setpoint
2nd
Second analogue input
D I/P
Digital input Enable
SW / DN
SW changeover/ Day night select DN On/ SW 0n (DN 0n)
TS-D
Day setpoint
TS-N
Night setpoint
TS-W
Winter setpoint
TS-S
Summer setpoint
PI limiter
PI limiter mode
MX / MN
Max. / Min. limit select
TL
Limiting temperature
REMOTE
Remote setpoint mode
Range
0...50 °C / 0...100 °C

Operating Modes

T
he POLYGYR-Ace has three different operating modes:
Setup mode: Used to configure the controller to the application. In this mode the controller is not in operation.
To get into setup mode: Press „Select"
process.
Test mode: Used to test the functioning of the controller and the installation. The controller operate normally, but
displays the following test values:
Output 1< > Output 2< > Analog Input 1< >
Analog Input 2 < > Digital Input.
To get into test mode: Press „Up"
Normal mode: As soon as the configuration has been finished, the controller goes into the normal operating mode.
Time-out
From any of the described modes the controller times out back to the normal operating mode.
From setup-mode:
after 30 secondes
From test-mode:
after 5 minutes
4
14.02.00
Display, Setting Range
−35...+130 °C
0...110 °C (20)
−35...+130 °C
On Off (Off)
0...110 °C (20)
0...110 °C (16)
0...110 °C (20)
0...110 °C (22)
Max.On/Min.On (Min.0n)
0....110 °C (16)
50 / 100 (50)

for more than 5 seconds. See next pages for explanations of the setup


and „Down"
key simultaneously.
CM2G3368X1
Name
Description
TEMP DIFF
Temperature difference mode
TDIFF
Temperature difference
TEMP SHIFT
Temperature shift mode
SF ST
Temperature shift start
SF ED
Temperature shift end
Shift
Temperature shift
O/P1
Output 1
O/P2
Output 2
XDZ
Dead Zone
TN
Integral time .....(OFF)
SD1
Switching differential for output 1
SD2
Switching differential for output 2
XP
Proportional band for 3 position
TCYC
Actuator cycle time for 3 position
Siemens Building Technologies / Landis & Staefa Division
Display, Setting Range
0...50 °C (0)
−35...+35 °C (26)
−35...+35 °C (30)
0... 35 °C (4)
Heat / Cool (Heat)
Heat / Cool / Off (Cool)
0...20 °C (2)
16, 32, 64...4096s (128)
0.5...10 °C (1)
0.5...10 °C (1)
1...100 °C (20)
30/90/120/150s (150)