Specifications
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Model:
SU1000XL
Series #:
AGSU1000DT
Input Voltage Range:
80-138 VAC
Output Voltage (Nominal):
120 VAC
Output Capacity (VA/Watts):
1000/800
Battery Runtime (Half/Full Load) Minutes:
18/6+
System Battery Voltage:
36 VDC
Recommended Dedicated
15 amp
Electrical Circuit Rating:
Approvals:
UL, cUL, NOM
FCC:
Class B
ALL UNITS: Input Frequency (50/60 Hz. Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave); Transfer Time: (0 ns.); Maximum
Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with Linear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours).
+ Battery runtime can be extended with addition of optional Tripp Lite External Battery Packs (sold separately). SU1000XL model uses BP36V13 battery packs.
SU2200XL and SU3000XL models use BP72V12-2U battery packs. External batteries will increase both the battery runtime and the battery recharge time.
* Since this model includes two plug options, the amperage of the recommended circuit would change to match the amperage of the plug. The output capac-
ity would also change based on the plug type used. SU2200XL includes a 20-amp NEMA 5-20P plug attached to its line cord, but also includes a 15-amp
NEMA 5-15P plug loose in the box that can be attached to the line cord by a qualified electrician.
FCC RADIO/TV INTERFERENCE NOTICE: (FOR CLASS A MODELS) Note: This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when oper-
ated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. Operation of this equipment is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense. The user must use shielded cables and connectors with this product. Any changes
or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
FCC RADIO/TV INTERFERENCE NOTICE: (FOR CLASS B MODELS) Note: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruc-
tion manual, may cause interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference using one or more of the following measures: reorient or relocate the receiving antenna; increase the sepa-
ration between the equipment and the receiver; connect the equipment into an outlet on a circuit different from that which the receiver is connected; con-
sult the dealer or an experienced radio/television technician for help. The user must use shielded cables and connectors with this product. Any changes or
modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. This
device complies with part 15 of the FCC rules. Operation is subject to the following 2 conditions: (1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
The SU1000XL is a Class B product based on the standard of the Voluntary Control Council for Interference (VCCI) from Information Technology
Equipment. If this is used near a radio or television receiver in a domestic environment, it may cause radio interference. Install and use the equipment
according to the instruction manual.
Note on Labeling
Two symbols are used on the label.
SU2200XL
AGSU2200DT
80-138 VAC
120 VAC
2200/1600*
18/6+
72 VDC
20 amp or 15 amp*
UL, cUL, NOM
Class A
V~: AC Voltage
V : DC Voltage
12
Manual del usuario
SU3000XL
AGSU3000DT
80-138 VAC
120 VAC
3000/2400
17/6+
72 VDC
30 amp
Sistemas UPS inteligentes realmente en línea para montaje en torre
UL, cUL, NOM
Class A
Modelos: SU1000XL, SU2200XL y SU3000XL
Importantes instrucciones de seguridad
Instalación
Operación básica
Localización de fallas
Almacenamiento y servicio
Especificaciones
English
Français
SmartOnline
• Operación realmente en línea • Salida sinusoidal pura
1111 W. 35th Street Chicago, IL 60609 EE.UU.
Atención al cliente: (773) 869-1234 • www.tripplite.com
© 2004 Tripp Lite. Todos los derechos reservados. SmartOnline
™
14
15
17
21
22
23