Application
DC Power
Input
RS485
POE
A Factory Default Reset (FDR) will return the ENGAGE Gateway settings to the original settings as
shipped from the factory. A FDR removes configurations, databases, and requires the device to be
recommissioned. A FDR will not remove the device from your ENGAGE account. If you wish to move a
Gateway to a different site you must first delete Gateway from site through with the mobile app. Then you
must FDR the gateway before you can commission into a new site.
A
Press and hold the FDR button.
Hold the button until the Gateway Status LED flashes green two times and remains solid. After the
indicator flashes twice, you may release the FDR button.
B
Wait for the Gateway to complete FDR.
After starting the FDR process the Gateway indicator will be solid green for a moment and reboot. The
reboot process can take a few minutes. During the boot process the Gateway indicator will be solid amber.
The Gateway will be in a factory default state when the indicator is solid red.
12
Cable/Wire Specifications
Part number
Belden 8760 or equivalent
Belden 9841 or 9842 or
equivalent, or as specified
by local electrical codes or
the ACP provider
Factory Default Reset (FDR)
Factory Default
Reset button
AWG
Description
18
2 Conductor
2 or 4 Conductor
24
shielded
CAT 5/6
Top View
Max distance
1000 feet
(305 meters)
4000 feet
(1219 meters)
300 feet
(100 meters)