Quick Parameter Reference, Faults and Alarms
Fault/Alarm
F0080:
Microcontroller watchdog fault.
CPU Watchdog
F0084:
Auto-Diagnosis Fault.
Auto-Diagnosis
Fault
A0090:
External alarm monitored through a
External Alarm
digital input.
Note:
It is necessary to program a digital input
for "No external alarm".
F0091:
External fault monitored through a digital
External Fault
input.
Note:
It is necessary to program a digital input
for "No external fault".
A0098:
General enable signal is missing during
Activate General
the self-tuning.
Enable
F0099:
The current measurement circuit is
Invalid Current
presenting an abnormal value for null
Offset
current.
A0110:
Fault detected through PTC type
High Motor
temperature sensors installed in the
Temperature
motor.
Note:
- It can be disabled by setting
P0351 = 0 or 2.
- An analog input and an analog output
must be set for the PTC function.
A0128:
It indicates that the inverter stopped
Serial
receiving valid telegrams during a certain
Communication
period.
Timeout
Note:
It can be disabled by setting
P0314 = 0.0 s
A0133:
It is the alarm indicating that the power
CAN Interface
supply is missing at the CAN controller.
without Power
Supply
A0134:
The inverter CAN interface has entered
Bus Off
the buss off state.
A0135:
It indicates a communication error alarm.
CANopen
Communication
Error
A0136:
The network master has entered the
Idle Master
idle state.
A0137:
It is the alarm indicating timeout of the
DeviceNet
DeviceNet I/O connections.
Connection
Timeout
A0138:
It indicates that the inverter received a
(2)
Profibus DP
command from the Profibus DP network
Interface in Clear
master to enter the clear mode.
Mode
24 | CFW700
Description
Possible Causes
Electrical noise.
Defect in the inverter internal circuitry.
Firmware incompatible with an accessory.
A digital input (DI1 to DI8) programmed for "No
external alarm" is open.
A digital input (DI1 to DI8) programmed for "No
external fault" is open.
The digital input programmed for "General Enable"
is open.
Defect in the inverter internal circuitry.
Excessive load at the motor shaft.
Severe duty cycle (too many Starts/Stops per
minute).
Too high surrounding air temperature.
Not installed motor thermistors.
Blocked motor shaft.
Check the wiring and the ground installation.
Make sure that the inverter has sent a new
message within the time interval set at P0314.
Broken or disconnected cable.
The power supply is turned off.
Incorrect communication baud rate.
Two network slaves with the same address.
Wrong cable connection (inverted signals).
Communication problems.
Wrong master configuration/settings.
Incorrect configuration of the communication
objects.
PLC in IDLE mode.
PLC command register bit set to zero (0).
One or more allocated I/O connections have
entered the timeout state.
Verify the network master status, making sure it is
in the execution mode (Run).
Refer to the Profibus DP communication manual
for more information
.
(3)