FILL-RITE FR1205C Manual D’utilisation Et De Sécurité

Ocultar thumbs Ver también para FR1205C:

Publicidad

Idiomas disponibles

Idiomas disponibles

FR1200C / FR2400C DC
FR4200D / FR4400 DC
SD1202 DC / FR600C / SD602 AC
FUEL TRANSFER PUMP
Owner's Operation & Safety Manual
for EXPLOSION-PROOF & RAIN-PROOF
Models FR1205C, FR1210C, FR1211C,
FR2410C, FR2411C, FR4210D, FR4211D,
FR4410, FR4411, FR610C, FR611C,
SD1202, SD602
FR610C
(shown)
SAFETY INSTRUCTIONS
To ensure safe and efficient operation, it is essential to read and follow
each of these warnings and precautions.
1. Do NOT smoke near pump or use pump near an open flame.
Fire could result.
2. Disconnect power to pump before servicing pump.
3. Take motors needing service to an authorized repair shop to
maintain "explosion-proof" and "rain-proof" integrity.
4. A Fill-Rite filter should be used on pump outlet to ensure that no
foreign material is transferred to fuel tank.
5. The pump motor is equipped with thermal overload protection.
If overheated, it will shut itself off without any damage to the
windings. Move ON / OFF lever to the 'OFF' position to reset
pump.
6. Tank or barrel should be anchored to prevent tipping in both
the full and empty conditions.
7. To minimize static electricity build-up, keep nozzle in contact
with container being filled.
DANGER
Electrical wiring should be done by a
licensed electrician in compliance with
local, state and national electrical code,
ANSI/NFPA 70, 30, 30A as appropriate.
Rigid conduit should be used and a
proper ground must be provided to avoid
the possibility of electrical shock. Failure
to comply with this warning could result
in serious injury and/or loss of property.
Use only static wire, conductive hose
when pumping flammable fluids.
WARNING
This product should not be used for fluid transfer into aircraft. This
product is not suited for use with fluids for human consumption or
fluids containing water.
FR1211C
(shown)
GENERAL DESCRIPTION
The Fill-Rite Series FR1200C, FR2400C, FR4200D, FR4400, FR600C,
SD1202, and SD602 products are positive displacement, rotary vane
pumps. Their rugged motors are explosion-proof and rain-proof to
ensure a long life of dependability.
Use Teflon® Tape on all pipe threads.
Do NOT install additional foot valves or check valves that do
not have a pressure relief valve.
DC PUMPS INSTALLATION INSTRUCTIONS
HEAVY DUTY:
1. Tightly screw suction pipe (1200KTG9099) into inlet flange
(1200F6465) of pumping unit.
2. Extend suction pipe into tank or barrel to within 3" of tank bottom.
Do not rest suction pipe on bottom of tank.
3. Screw inlet flange of pump into tank or barrel opening. Inlet flange
must be completely and securely threaded into an undamaged tank
or barrel bung.
STANDARD DUTY:
1. Secure nozzle boot (1200G8521) to motor endplate with the
two supplied bolts (300F7751) as illustrated on Page 3 of
manual.
2. Tightly screw extension pipe (VP1400F7687) into bung adapter.
Attach suction pipe (VP1400F7686) to extension pipe in the
same manner.
3. Cut suction pipe at a length that will place its end within 3" of the
container bottom. If a longer suction pipe is required, order
additional extension (VP1400F7687).
4. Screw bung/suction pipe assembly securely into container
opening.
HEAVY DUTY AND STANDARD DUTY (Electrical)
1. Install pump. Read and understand all of the electrical wiring
instructions before proceeding.
2. If pump does not have proper grounding, meaning continuous metal
to metal connection from one component to the next, including tank,
bung, pump, meter, filter, hose and nozzle, the pump needs to be
electrically bonded to supply tank or vehicle frame. To electrically
bond pump, remove green bonding screw located next to junction
box cover. Insert this screw through eyelet of furnished green
bonding wire assembly and refasten it securely to the pump. The
other end of the wire is to be stripped of insulation and the bare wire
securely bonded to the vehicle frame or skid tank.
CAUTION: Do not connect the positive or negative power to
the green screw or wire as this could cause a fire.
3. Remove pump's electrical junction box cover and straighten the 2
wires to make the stripped wire ends accessible outside of the
junction box.
4. Screw furnished cable connector into ½ inch NPT conduit opening
in pump junction box.
5. Strip 6 inches of the outer covering from one end of the furnished
electrical cable being careful not to damage the black and red wire
insulation.
6. Loosen cable connector nut and pass the stripped end of the
furnished cable through the cable connector until 2 inches of the
unstripped cable is within the cable connector. Tighten the cable
connector nut.
7. Strip ½ inch of the installation from the ends of the red and black
cable wires. Using the furnished wire nuts, connect these wires
to the pump wires matching the colors. Be sure no bare wire is
exposed.
8. Fold wires into junction box and replace cover making sure the
gasket is in place. Make sure all screws are seated so there is
no space between the cover and the junction box.
1
ALL PUMPS

Publicidad

Tabla de contenido
loading

Resumen de contenidos para FILL-RITE FR1205C

  • Página 1 “explosion-proof” and “rain-proof” integrity. 2. If pump does not have proper grounding, meaning continuous metal 4. A Fill-Rite filter should be used on pump outlet to ensure that no to metal connection from one component to the next, including tank, foreign material is transferred to fuel tank.
  • Página 2 For Vehicle Installation D. Check all connections to make sure they are connected per Follow steps 1 through 8 on Page 1. A. Pass the electrical wires to the source of the vehicle power instructions and all electrical codes. Install the 30 amp slow blow system, supporting the wires as necessary and protecting it from fuse in the fuse holder.
  • Página 3: Parts List

    PARTS LIST ITM PART PART DESCRIPTION NO. NO. DESCRIPTION 1 1200F6465 Inlet Flange 20 700F3135 3/4" x 12' UL Listed Hose (FR610C, SD602) 1 2 100F0760 Screen FRH07512 3/4" x 12' Hose(FR1200C,FR2400C,SD1202 1 3 100F0790 Inlet Gasket FRH10012 1" x 12' Hose (FR4200D, FR4400) 4 1200F2756 Bypass Valve 21 1200KTG9099 Suction Pipe Steel (Heavy Duty)
  • Página 4 Tuthill Transfer Systems (“Manufacturer”) warrants to each consumer constitute the sole recourse of the Buyer against Manufacturer for buyer of its Fill-Rite products (the “Buyer”), from the date of invoice or breach of warranty. IN NO EVENT SHALL MANUFACTURER’S sales receipt, that goods of its manufacture (“Goods”) will be free from LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF THE defects of material and workmanship.
  • Página 5 “certificado a prueba de lluvia”. 1. Instale la bomba. Antes de proceder lea y entienda todas 4. Se deberá usar un Fill-Rite filtro en la salida de la bomba para las instrucciones de cableado eléctrico. asegurare de que no se transfieren materiales extraños al tanque de combustible.
  • Página 6 Pele 1/2 pulgada de la aislación de los extremos de alambres los ATENCIÓN: No intente alimentar energía a la bomba cable rojo y negro. Usando las tuercas de alambre provistas, desde un cableado delgado del motor tal como el conecte esos cables a los cables de la bomba con colores cable del encendedor de cigarrillos.
  • Página 7: Lista De Piezas

    LISTA DE PIEZAS PIEZA ITM PIEZA DESCRIPCIÓN NO. NO. DESCRIPCIÓN 1 1200F6465 Brida de entrada 20 700F3135 Manguera listada por UL de 12 pies 2 100F0760 Rejilla FRH07512 Manguera 3/4"x12pies(FR1200C,FR2400C 3 100F0790 Junta de entrada FRH10012 Manguera 1" x 12 pies (FR4200D, FR4400) 4 1200F2756 Válvula de desvio 21 1200KTG9099 Tubo de aspiración, acero (Pesado)
  • Página 8 Tuthill Transfer Systems ("Fabricante") garantiaz a cada comprador NINGÚN CASO SERÁ EL FABRICANTE RESPONSABLE POR DAÑOS consumidor de sus productos Fill-Rite (el "Comprador"), a contar de CONSECUENTES, NI SERÁ EL FABRICANTERESPONSABLE POR la facturacion o boleta de venta, que la mercancía de su fabricación RECLAMACIONES DE DAÑOS QUE SURJAN DE LA FABRICACIÓN,...
  • Página 9: Pompe De Transfert De Carburant

    1. Installez la pompe. Lisez et assimilez toutes les 4. Un Fill-Rite filtre doit être utilisé à la sortie de la pompe pour éviter instructions de câblage électrique avant de commencer. la rentrée de corps étrangers dans le réservoir de combustible.
  • Página 10 4. Vissez le connecteur de câble fourni dans l’ouverture pour C. Fixez une extrémité du porte-fusible sur l’extrémité du fil qu’il conduit NPT 13 mm (1/2") dans la boîte de raccordement de la vous reste. Réalisez un solide raccordement électrique avec pompe.
  • Página 11 LISTE DES PIÉCES DÉTACHÉES ART. RÉFÉRENCE ART RÉFÉRENCE NO. NO. DESCRIPTION QTÉ DESCRIPTION QTÉ 1 1200F6465 Bride d'entrée 20 700F3135 Tuyau agréé par UL de 3/4x12'(610C,602) 2 100F0760 Grille FRH07512 Tuyau 3/4 x 12' (FR1200C, FR2400C) 3 100F0790 Joint d'entrée FRH10012 Tuyau 1 x 12' (FR4200D, FR4400) 4 1200F2756...
  • Página 12: Garantia

    Tuthill Transfer Systems ("Fabricant") garantit à l'acheteru de ses produits LIVRAISON OU L’UTILISATION DES MATERIELS SERA LIMITEE AU PRIX Fill-Rite ("Acheteur") à compter de la date de facturation ou du recu de vente D’ACHAT DE CES MATERIELS. que les produits fabriqués ("Produits") sont exempts de défauts de Cette garantie ne s’appliquera pas à...

Tabla de contenido